AVTECH Software Inc.
17
Room Alert 26W
Configuration And Setup Screens
Digital sensors are those that provide real-time variable status values that can be used to obtain a more
definitive understanding of a current sensor’s status, allow products like PageR to monitor at multiple
thresholds and be logged for historical reference. These values are included within alert messages for
a clearer understanding by recipients and used for trending or manipulation into graphs or charts via
other applications. These sensors attach to various AVTECH hardware via RJ-11 cable to an external
environment sensor channel. Current sensors providing real-time values include the AVTECH Digital
Temperature Sensor, AVTECH Digital Humidity Sensor and AVTECH Digital Power Sensor.
Digital Temperature Sensor
Digital Temperature/Humidity Sensor
Digital Power Sensor
Switch Sensors
Switch sensor alert thresholds are set using the ‘Switch 1-8’ and ‘Switch 9-16’ tabs. The appropriate sensor
number to configure will be determined by the set of sensor contacts on the back of the Room Alert 26W unit
that the corresponding sensor is connected to. The circuit or sensor state selected in the ‘Alarm On’ drop-down
menu should be the circuit state that you wish alert notifications to be sent at. To determine the proper sensor
state, connect the sensor to the Room Alert 26W unit and determine the current circuit state displayed on the
‘Status’ screen for that sensor. Enter the opposite sensor state in the ‘Alarm On’ drop-down menu for that sensor. If
there is no sensor connected to a specific sensor channel, choose ‘Disabled’ from the ‘Alarm On’ drop-down menu.