Dip switches
Dial tone
continuous tone
(other european countries)
DIP 1 in ON
cadenced tone
(for Italy)
DIP 1 in OFF
PSTN line fault detection procedure
PSTN line voltage moni PSTN line activity monitoring
(PSTN line dial
tone signal is NOT supervised)
DIP 2 in ON
PSTN line voltage moni PSTN line valid dial tone moni
PSTN line activity monitoring
(no activity for 60 seconds = fault)
DIP 2 in OFF
PABX connection
If
VECTOR Plus
interface were to be installed in premises where PABX equipment is present,
requiring additional digits when dialling to reach external telephone line (Ex. 0 or 9):
connection through PABX: the interface eliminates the first digit of
telephone number when dialling through the GSM.
DIP 3 in ON
direct connection to external telephone line
DIP 3 in OFF
Important
always ON
DIP 4 in ON
Factory defaults
DIP 4 ON
DIP 3 OFF
DIP 2 OFF
DIP 1 OFF
LEDs
LD1:
shows the GSM module operation status:
flashing -
GSM module is registered in the
network and in stand-by;
on -
a GSM call is taking place;
off -
the GSM module is NOT correctly
registered in the network
(failure condition)
LD2:
must be always ON indicating that the GSM module is working.
(NOTE: this two leds will activate only when using the industrial GSM module)
Input and output
"GSM" input:
when connected to negative forces the operation in GSM mode, for installations
where PSTN line is not available. All PSTN line monitoring functions are disabled.
TT output:
Tamper output
to be connected to a 24 hous loop of the control panel.
OC1 output:
open collector output activated when PSTN line fault is detected.
OC2 output:
open collactor output activated when GSM failure is detected.
OC3 output:
not used
Settings
RV3
(Adjust only if needed)
It is used to adjust the frequency of the telephone line signals generated
by
VECTOR Plus
(dial tone and busy tone = typical 425Hz)
in the case the dialler connected to it were
to have some difficulties in recognizing them.
6