To enter Manual Calibration, Press the 

SEL

 Key until MAN CAL is shown on the display 

will show FWGN xx. Repeatedly pressing the 

SEL

 switch will cycle through what can be 

changed. 
FWGN  xx 
RVGN  xx 
DR ENABL  or  DR DISAB    based upon what is set 
ZERO  xx 
SPAN  xx 
DIR ACTG  or  REV ACTG   based upon what is set 
TX FT LO     or  TX FT HI     based upon what is set 
REG CAL 
RESTORE FACTORY DEFAULT 

 

4.4.1   Forward Gain (FWGN  XX

) is the gain applied when opening the valve. 

o

 

The LCD shows “FWGN  xx” where xx is the current gain.  

o

 

Pressing the DOWN Key decreases the gain 

o

 

Pressing the UP        Key increases the gain 

 

4.4.2    Reverse Gain  (RVGN  XX) is

 the gain applied when closing the valve. 

 
The LCD shows “FWGN  XX” press the CAL Key again and the LCD shows “RVGN XX”.   
RVGN xx changes can now be made. 
Pressing the DOWN Key decreases the gain 
Pressing the UP        Key increases the gain 

 

4.4.3    Drop off  (DR ENABL or DR DISAB)

  -  Enables or Disables Drop off at end of travel  

 

The LCD shows “RVGN  XX” press the CAL Key again and the LCD shows either “DR ENABL 
or DR DISAB”  .   DR ENABL or DR DISAB  can now be selected. 
Pressing the DOWN or UP Key toggles this setting. 

4.4.4    Zero Position  (ZERO XX)  - 

 Adjusts the electronic stop away from (increasing values) or 

towards (decreasing values) from the physical closed position. 0 being nominally the 
position of the hard stop zero and 100 being about 90 degrees away from it 

 

The LCD shows “DR ENABL or DR DISAB”  press the 

CAL

 Key again and the LCD shows 

“ZERO xx”.   ZERO XX changes can now be made. 
Pressing 

UP

 Key increases the zero position of the valve away from the hard stop.  

Pressing 

DOWN

 Key moves the zero position closer to the hard stop.  

 

Содержание EaziCal II

Страница 1: ...OM Tech 537 Revision Prepared By Peter Keating Date 10 25 2017 Drafting Work Order 23142 ECN Reviewed By Chris Irwin Date 1 5 2018 Approved By Jason Moorehead Date 1 5 2018 This IOM contains confident...

Страница 2: ...4 7650 FAX 201 794 0913 www avidcontrols com 01 05 2018 TECH 537 D W O 23142 Page 2 of 21 Revision History Revision 01 05 2018 Initial release Locations USA Phone 201 794 7650 Europe Phone 011 44 189...

Страница 3: ...TECH 537 D W O 23142 Page 3 of 21 Table of Contents 1 Introduction 4 1 1 Product Certification 4 1 2 Warnings 4 1 3 Description 5 1 4 Principles of Operation 5 1 5 Special Features 6 2 Order Guide 7 3...

Страница 4: ...y be equipped with either two 3 wire switches or two 2 wire inductive sensors 1 2 Warnings WARNING The aluminum housing Model EaziCal II Ex ia is at potential risk of ignition by impact or friction th...

Страница 5: ...ner comes standard with 4 20mA feedback transmitter In addition there are options for feedback limit switches Mechanical proximity inductive proximity type 1 4 Principles of Operation The EaziCal II u...

Страница 6: ...Gain Zero and Span positions o LCD displays loop current valve position Integrated Transmitter The transmitter operates from the same sensor input as the main unit but is powered by a separate loop It...

Страница 7: ...itches 203 2 x P F NJ2 V3 N 210 2 x IFM IS5026 Non Hazardous ONLY No Approval 211 2 x IFM IS5001 Non Hazardous ONLY No Approval 216 2 x Gold Plate Mechanical SPDT 257 2 x P F NBB2 V3 E2 3G 3D Non Haza...

Страница 8: ...quipment This symbol identifies information about operating the equipment in a particular manner that may damage it or result in a system failure Failure to heed this warning can lead to total failure...

Страница 9: ...to the actuator inlet port that acts against the spring Increasing signal causes pressure to increase in Outlet Port 1 of the positioner Double Acting Actuator Double Return For double acting actuato...

Страница 10: ...Transmitter Function is being automatically calibrated during this procedure Time for the first move in calibration will be set at a maximum of 30 seconds for REG CAL and all subsequent time outs are...

Страница 11: ...A Split Range High calibration refers to the input current value that drives the valve into the Span position The Transmitter Function is being automatically calibrated during this procedure First fol...

Страница 12: ...ied when closing the valve The LCD shows FWGN XX press the CAL Key again and the LCD shows RVGN XX RVGN xx changes can now be made Pressing the DOWN Key decreases the gain Pressing the UP Key increase...

Страница 13: ...or TX FT HI TX FT LO or TX FT HI can now be selected Pressing the DOWN or UP Key toggles this setting 4 4 8 Calibration Timeout REG CAL or LONG CAL Time for the first move in calibration will be set a...

Страница 14: ...y Default Settings Press SEL Key until the LCD scrolls Restore Factory Default Press Down arrow until LCD reads Hold Key Press and hold Key LCD will scroll Factory Default Success Factory default sett...

Страница 15: ...r please ensure that the process is safe to do so and that all hands are kept away from the moving shaft cams Stroke the actuator from one end of travel to the other several times to check the switch...

Страница 16: ...s com 01 05 2018 TECH 537 D W O 23142 Page 16 of 21 Wiring Diagrams Figure 6 No Switch option Figure 7 SPDT mechanical switches Figure 8 SPDT T Switch proximity switch Figure 9 Namur Inductive proximi...

Страница 17: ...igh Flow please contact the factory Important The positioner s onboard filter is not a substitute for normal instrument air preparation Supply air to the positioner should conform to ISA Standard S7 3...

Страница 18: ...MIDLAND AVENUE STE 258 SADDLE BROOK NJ 07663 TEL 201 794 7650 FAX 201 794 0913 www avidcontrols com 01 05 2018 TECH 537 D W O 23142 Page 18 of 21 7 Appendix Appendix A Intrinsically Safe wiring Contr...

Страница 19: ...reforming an Auto Calibration and within 2 minutes the LCD displays UNABLE TO CLOSE The air supply is not connected or turned on CURRENT OUT OF RANGE Input current set too high for Low current Calibra...

Страница 20: ...CRANE Co 280N MIDLAND AVENUE STE 258 SADDLE BROOK NJ 07663 TEL 201 794 7650 FAX 201 794 0913 www avidcontrols com 01 05 2018 TECH 537 D W O 23142 Page 20 of 21 Appendix C Dimensions...

Страница 21: ...OFF PRESS AND RELEASE SEL UNTIL DR ENABL OR DR DISAB SHOWS IN DISPLAY PRESS OR TO ENABLE DISABLE DROP OFF ZERO ADJUST PRESS AND RELEASE SEL UNTIL ZERO SHOWS IN DISPLAY PRESS OR TO ADJUST THESE VALUES...

Отзывы: