Signals for the EP applicator
For controlling the applicator the signals air stream, cylinder valve and blow on are necessary.
After a product signal has occurred the labelling cylinder valve is switched active after the delay
STAD. However if at this time the applicator is not in the home position then error message
E__2 is generated. After the delay time APT1 the blow on valve is switched active for the time
APT2.
When APT2 is completed both the labelling cylinder valve and the blow on valve signals are
switched inactive. If the control does not read the home position in the time given - 3* (APT1+
APT2) - than the error message E__2 is generated.
Productstart
Cylinder valve
Dispense label
+ Airstream valve
Blowon valve
Homeswitch
1
2
Missing Label: Labeller not ready for dispense
Error: Applicator not in homeposition
3
Error: Homeposition not detected
STAD
APT1
APT3
APT2
1
3
STAD
STAD
APT1
4 * (APT1 + APT2)
STAD
2
Figure 19 Timing EP applicator
Содержание ALS 330
Страница 1: ...Ausgabe 08 07 Artikelnummer 0089999 06...
Страница 2: ......
Страница 6: ...Operators Manual ALS 330 430 Release 8 07 Contents...
Страница 18: ...Operators Manual ALS 330 430 Release 8 07 Page 16 Description...
Страница 37: ...Operators Manual ALS 330 430 Release 8 07 Page 35 Operation...
Страница 38: ......
Страница 50: ......
Страница 73: ...Operators Manual ALS 330 430 Release 8 07 Page 65 Connections and signals l Figure 29 Internal I O connector...
Страница 75: ...Operators Manual ALS 330 430 Release 8 07 Page 67 Connections and signals 8 5 Electronic diagrams...
Страница 76: ...Operators Manual ALS 330 430 Release 8 07 Page 68 Connections and signals Figure 30 Wiring diagram...
Страница 79: ...Operators Manual ALS 330 430 Release 8 07 Page 71 Connections and signals...
Страница 80: ......
Страница 84: ...Operators Manual ALS 330 430 Release 8 07 Page 76 Errors and warnings...
Страница 92: ......