General instructions
W
Observe the regulations for accident prevention and environmental protection.
W
Observe the safety instructions and regulations of the country in which the product is used
or operated.
W
Only use AVENTICS products that are in perfect working order.
W
Follow all the instructions on the product.
W
To avoid injuries due to unsuitable spare parts, only use accessories and spare parts
approved by the manufacturer.
W
Comply with the technical data and ambient conditions listed in the product documentation.
W
You may only commission the product if you have determined that the end product (such as
a machine or system) in which the AVENTICS products
are installed meets the country-specific provisions, safety regulations,
and standards for the specific application.
W
Bus couplers contain components that are sensitive to electrostatic. If they are touched, this
may lead to an electrostatic discharge that could damage or destroy them. Only remove the
device from the ESD protective bag after the potential
has been equalized. Avoid direct contact with electronic components and wear
a ground bracelet.
W
Do not put the valve system into operation before it is completely assembled
as well as correctly wired and tested.
W
Always make sure that the relevant system part is not under voltage or pressure before you
install or remove the bus coupler.
W
Dispose of the product in accordance with the currently applicable regulations
in your country.
3
Delivery Contents
W
1 BDC-S bus coupler with AS interface in an ESD protective bag
W
1 seal
W
Mounting screws
W
1 set of operating instructions
4
About This Product
The bus coupler has 8 inputs and 8 outputs. It can be switched to 16 outputs
(default factory setting: 16 outputs).
The bus coupler therefore occupies two or four bus addresses on the sensor actuator bus line
(AS-i network).
Product overview
The control elements, the LED displays, and the bus coupler connections are shown in
Figures
to
.
Top: LEDs
LED AS-i 1
to
LED AS-i 4
:
Diagnosis for AS bus connection
FAULT LED
:
Malfunction
AUX LED
:
Valve power supply
LED IN 1.0
to
LED IN 2.3
:
Sensor signal diagnosis LEDs
1
4
BDC AS-i
AS-i 1
FAULT 1
AS-i 2
FAULT 2
AS-i 3
FAULT 3
AS-i 4
FAULT 4
AUX
IN 1.0
IN 1.1
IN 1.2
IN 1.3
IN 2.0
IN 2.1
IN 2.2
IN 2.3
1
Bottom:
S1
to
S4
and
X2O
Front:
X2I1
to
X2I4
Table 10: Meaning of the LED displays
AS-i 1 to AS-i 4
(green)
FAULT 1 to FAULT 4
(red)
Meaning
Off
Off
No AS bus line (yellow cable)
power supply
On
Off
Cyclic I/O data traffic
On
On
No I/O data traffic
On
Flashes
The sensor supply is short-circuited or
overloaded. Status bit S1 is set.
AUX (green)
Meaning
Off
No valve power supply present (black cable)
On
Valve power supply present (black cable)
IN 1 to IN 4 (green)
Meaning
Off
No sensor signal present on the IN X input
On
Sensor signal present on the IN X input
S1
to
S4
:
Sliding switch for switching between the variant with 16 outputs and the
variant with 8 outputs
X2O
:
25-pin D-Sub plug connection for connecting to the valve system
X2I1
to
X2I4
:
M12 sockets for connection of 2-wire and 3-wire sensors
4
3
2
1
S1
S2
S4
S3
X2O
2
X2I1
X2I2
X2I3
X2I4
3
AVENTICS
| AS-i | R412008327–BDL–001–AB | English
5