Part 2. Outdoor unit:
This chart shows the the dismantlement process of outdoor unit of heat pump model..The only cooling
model can refer to this flow:
figure1
figure2
1. Loosen the two bolts on the electrical cover
(
as shown in chart 1) Take down the electrical cover
unit.
2. Loosen the two bolts on the 3 fixed wire calmp. loosen the bolt on fixed powerline and
communication lines of inside and outside unit. take down the power connecting wire and inside and
outside unit communication lines. (as shown in figure 2)
3. The rewiring must strictly follow chart 3.The communication lines of A B systems (including NO. 1
and 2 wires and NO. 3 and 4 wires in a same line) cannot be reversed.
figure3