8
ASW-12A+12A
2
/
EA(L)
2-
III
Model No
Items
Indoor Unit A
(System A)
Indoor Unit B
(System B)
Outdoor Unit
Type
Wall mounted model Heating pump
Cooling kw
3.2
3.2
/
Dehumidify kg/h 1.
1
1.1 /
Heating kw
/ / /
Noise level
dB(A)
41
41
62
Cooling 2.56
2.56
/
Performance
EER
Heating
W/W
2.56 2.56 /
Power supply
φ
-V-Hz
1 / 2
08
-2
3
0V~/
6
0Hz
Cooling 1250
1250
2500
Rated input
Heating
W
/ / /
Cooling 5.7
5.7
11.4
Rated current
Heating
A
/ / /
Length m
2
2
4.8
Supply cord
Class
/
250V 10A
250V 10A
400V 25A
Starting Current
A
30.5
30.5
/
Electrical Data
Fuse capacity
A 3.15
3.15 3.15
Refrigerant/Charge g
R22/1280 R22/1280 /
Type /
Rotary
Rotary
/
Model /
2P20S236A1G 2P20S236A1G /
Rated input W
1235
1235
/
Compressor
Overload
Protector
/ Outer
Outer
/
Heat exchanger
Row*Hole
2*13
2*13
2*31
Type Capillary
tube
Refrigerating System
Expansion device
Specification(mm)
φ
3.0*1000
φ
3.0*1000
/
Air Volume
m3/h
520
520
/
Cooling r/min
1180/1050/900/800
1180/1050/900/800
860
Fan Speed
H/M/L/Q
Heating r/min
/
/
/
Fan type
/
Cross flow
Cross flow
Propeller fan
Fan System
Fan motor output
W
19
19
68
Connecting
Pipe
Gas /Liquid OD(mm)*L(mm)
Φ
9.52×5000/
Φ
6.35×5000
Connection
Drainage Pipe
OD(mm)*L(mm)
Φ
14×780
Suitable area
m2
12-21
12-21
/
Net dimensions
(W x H x D)
mm 745*250*210
745*250*210
331*846*901
Others
Net
weight kg 10.5
10.5 75
Содержание EA Series
Страница 1: ...AUX One to Two Split Air Conditioner Service Manual EA EL HS Series ...
Страница 48: ...AUX Air Conditioner Service manual 46 9 Fault analysis of major parts ...
Страница 58: ...AUX Air Conditioner Service manual 56 b Single Cooling Model ...
Страница 59: ...3 Wiring diagram for Original Multi type a Indoor unit Wiring diagram b Outdoor unit Wiring diagram 57 ...
Страница 60: ...AUX Air Conditioner Service manual 57 Section 10 Service Record Date Page Part Cause Report ...