Output frequency: F = Fo +
Δ
F
Δ
F =Kp×
(
En+1- En
)
+ Ki×En+1 + Kd×
(
En+1 - 2En + En-1
)
Fo=20
,
Kp=6.0, Ki=8.0, Kd=2.0 (EEEPROM can adjust)
a.Frequency range: 20Hz
~
85Hz;If F
<
20Hz,the less should be 20Hz;If F
>
85Hz ,the
most should be 85Hz;
b. En+1=Ts - Tr
,
the range of En+1
:
-3
~
+13
;
c.If En+1
≤
-2,it continue at 2 min and then shut down the compressor;
d.If En+1
<
0 when it starts,compressor false to start.or compressor is able to start;
e.No temperature compensation at the first run and then go to the temperature
compensation when compressor start,the compensation data in the EEPROM such as
compensate 3 and Tr=Tr(real dat)
℃
- 3 ;
℃
5
、
Set auto
、
high
、
middle and low wind speed according to requirement at the heating
mode,auto wind speed should be:
If Tr
≤
Ts-5 ,it should be high wind speed;
℃
If Ts-5
℃
<
Tr
≤
Ts-3 ,it should be middle wind speed;
℃
If Tr
≥
Ts-3 ,it should be low wind speed;
℃
No delay for wind speed at the auto wind speed when change from low wind speed to high
wind speed;or delay for 3 mins;
6
、
Include timer
、
sleep
、
auto restart
、
anti-cool
、
auto anti-frost
、
high efficiency running at the
cooling mode;the button of air blade control the movement and stop of air blade;
7
、
Include overheating protection of indoor pipe,overflowing protection,overheating protection
of compressor,trouble protection of indoor motor,trouble protection of sensor,trouble
protection of module,trouble protection of communication,3min delay protection of
compressor,specific information for the function indication of trouble protection ;
8
、
For compressor No 3min delay protection at the first start;
9
、
Flowing heat:indoor motor run at the lower wind speed when shut down by the remote
controller or lash-up button and indoor air blade blow the leaving heat when compressor delay
15s to shut down.indoor motor and air blade will be shut down if Te
<
40 when compressor’s
℃
off;
10
、
Four way valve and outdoor motor start when compressor run for 5s and outdoor motor
will be shut down after compressor’s off for 15s when it turn off or mode changes,four way
valve start when compressor for 2min50s;
11
、
Anti-cool
This function have priorty to wind speed limitative function,specific operation as follows:
When compressor run:Te at the upper trend
a)
、
When Te
<
25 ,indoor motor stop;
℃
25
Содержание ASW-H09A4/SAR1DI
Страница 1: ...FOR Split Wall Mounted Series R410a DC Inverter ASW H09A4 SAR1DI ASW H12A4 SAR1DI 2008 ...
Страница 6: ...Remote Controller Instructions 4 ...
Страница 7: ...5 ...
Страница 8: ...6 ...
Страница 9: ...7 ...
Страница 10: ...8 ...
Страница 11: ...9 ...
Страница 12: ...10 ...
Страница 13: ...11 ...
Страница 14: ...12 ...
Страница 15: ...13 ...
Страница 16: ...14 ...
Страница 17: ...15 ...
Страница 42: ...Exploded Pictures 1 Indoor unit exploded picture ASW H09A4 SAR1DI 40 ...
Страница 44: ... 2 Outdoor unit exploded picture ASW H09A4 SAR1DI 42 ...
Страница 46: ... 3 Indoor unit exploded picture ASW H12A4 SAR1DI 44 ...
Страница 48: ... 2 Outdoor unit exploded picture ASW H12A4 SAR1DI 46 ...