CONTENTS 

 
Product Specifications…………..……………………………………………..1 

 

Dimensions………………………………………….………………………………2 

 

Refrigeration Cycle Diagram……………………………………………….…3 

 

Remote Controller Instructions………………..……………………………4 

 

Brief Introduction Of Installation………………………………………….16 

 

Wiring Diagram………………………………………….……………………….20 

 

Operation Details…………………………………………………………..…..22 

 

Disassembly Of The Parts…………………………..……………..………..36 
 
Exploded Pictures……………………………………………………………...40 

 

Содержание ASW-H09A4/SAR1DI

Страница 1: ...FOR Split Wall Mounted Series R410a DC Inverter ASW H09A4 SAR1DI ASW H12A4 SAR1DI 2008 ...

Страница 2: ...Specifications 1 Dimensions 2 Refrigeration Cycle Diagram 3 Remote Controller Instructions 4 Brief Introduction Of Installation 16 Wiring Diagram 20 Operation Details 22 Disassembly Of The Parts 36 Exploded Pictures 40 ...

Страница 3: ...ling 10 4 8 09 13 0 11 5 8 4 10 9 E E R Heating BTU h W 9 88 7 31 12 6 10 4 9 0 12 7 Dehumidifying Kg h 1 2 1 4 Power Supply φ V Hz 1 220 240 50 Indoor 420 580 Air Circulation Outdoor m3 h 800 800 Indoor 39 42 Noise Level Outdoor dB 53 53 Indoor 19 19 Motor Input Outdoor W 35 35 Indoor 802 265 185 880 286 196 Dimension WxHxD Outdoor mm 818 320 540 818 320 540 Indoor 9 5 11 Net Weight Outdoor kg 36...

Страница 4: ...ensions 1 Indoor unit MODEL ASW H09A4 SAR1DI ASW H12A4 SAR1DI DIM W mm 802 880 H mm 185 196 D mm 265 286 2 Outdoor unit MODEL ASW H09A4 SAR1DI ASW H12A4 SAR1DI DIM W mm 760 760 H mm 540 540 D mm 260 260 2 ...

Страница 5: ...Refrigeration Cycle Diagram Pipe size Diameter Ø Max Piping Length Max Elevation MODEL m m Liquid inch Gas inch ASW H09A4 SAR1DI 1 4 3 8 15 3 4 ASW H12A4 SAR1DI 1 4 3 8 15 3 4 3 ...

Страница 6: ...Remote Controller Instructions 4 ...

Страница 7: ...5 ...

Страница 8: ...6 ...

Страница 9: ...7 ...

Страница 10: ...8 ...

Страница 11: ...9 ...

Страница 12: ...10 ...

Страница 13: ...11 ...

Страница 14: ...12 ...

Страница 15: ...13 ...

Страница 16: ...14 ...

Страница 17: ...15 ...

Страница 18: ... order Selection of the installation position Installing the air conditioner 16 Expelling the air in the pipes and the indoor unit Connecting the pipes and wires Testing 2 Selection of the installation position Indoor Unit There is no heating and steaming source nearby No obstacles for installation position from nearby Keep good air circulation Convenient to adopt measures to reduce noises Don t i...

Страница 19: ...Otherwise it might cause water drips when air conditioner is running in cooling operation Drill 70mm diameter pipe hole at the left lower or right lower side of the installation board The hole shall slant outward slightly Hang the indoor unit to the oard and make sure the machine is in the middle of the board Push the machine towards the left lower and right lower side of the installation board un...

Страница 20: ...on material and fix them with two plastic rings Wrap up the pipes with tape alongside the wall and fix them to the wall with clips These steps are usually adopted when outdoor unit is installed below the indoor unit In case that you want to have additional water discharge pipe the end of pipe should be within certain distance from the floor to prevent water from draining back into the pipe Fix it ...

Страница 21: ...crew take off the control panel cover from the unit Cooling type connect the wire to the related connection point on the panel and connect the signal connection plug Remarks yellow and green cord should be connected to connection point with mark Fasten the fixture of wire to control panel Screw up the control panel cover to its original place 9 Test running Make sure that the pipes and wires are c...

Страница 22: ...1 Indoor Unit Electric Chart S N L Temperature Sensor Power plug 220 240V 50Hz Fan Motor Display receive Panel Transformer Step Motor Controlling board To Outdoor Unit Indoor Unit Electric Chart 8R032GRN861 0017 G 20 ...

Страница 23: ...IPM board U V W DC_N DC_P N_OUT L_OUT PFC DC_P DC_N DC_P DC_N DC_P DC_P 12V 5V G CON6 CON17 N To Indoor Unit RS G N_IN L_IN Outdoor Unit Electric Chart 8R032GRW861 0006 power board Temperature Sensor Orientation Valve 4WV_L 4WV_N TOP CAP L N Fan Motor EXHAUST Compressor CON19 21 ...

Страница 24: ...g according to cooling mode temperature setting is Tr 2 3 when 23 Tr 25 choosing dehumidification mode and running according to dehumidification mode temperature setting is Tr 2 4 when Tr 23 choosing heating mode and running according to heating mode temperature setting is 26 5 The functions of this model are as follows time setting sleep auto start Anion I feel and so on 6 After selecting the sys...

Страница 25: ...e it can set as automatic wind high wind medium wind low wind to meet requirement and the automatic wind speed can controlled as follows when Tr Ts 3 High wind when Ts 1 Tr Ts 3 Medium wind when Tr Ts 1 low wind At automatic speed when the wind speed from low switching high the wind speed without delay while from high switching low there will be delay with 3 min 6 The functions of this model are a...

Страница 26: ...operational mode it can set as automatically high medium low wind and the automatic wind speed can controlled as follows when Tr Ts 5 high speed when Ts 3 Tr Ts 5 medium speed At automatic speed when the wind speed from low switching high the wind speed without delay while from high switching low there will be delay with 3 mins 5 The functions of dehumidification are as follows time setting auto s...

Страница 27: ...nti frost high efficiency running at the cooling mode the button of air blade control the movement and stop of air blade 7 Include overheating protection of indoor pipe overflowing protection overheating protection of compressor trouble protection of indoor motor trouble protection of sensor trouble protection of module trouble protection of communication 3min delay protection of compressor specif...

Страница 28: ...er wind speed Or when Te 25 indoor motor shut down b When Te go up and Te 28 indoor motor blow the lower wind speed Or when Te 28 indoor motor shut down 12 Compare to protect the Ta Indoor temperature at the heating mode When Ta 22 it s able to run at the heating mode and the highest working frequen cy of compressor is 50Hz When 22 Ta 10 it s able to run at the heating mode and the the highest wor...

Страница 29: ...e following condition 1 Temperature of outdoor heat exchanger 13 at the consecutive 80s 2 The consecutive time of anti frost 9min EEEPROM can adjust 4 Anti frost exit Compressor stop to run and outdoor motor start when compressor stop to run for 50s and then compressor s 7 Sleep Control Sleep function is available at the auto cooling heating mode and indoor motor run at the lower wind speed at the...

Страница 30: ... 33 44 for 1sÆLight run for 1sÆTiming run for 1sÆSleep light run for 1sÆStep motor run for 1sÆindoor motor run for 1s at its full wind speedÆBuzzer ring for 1 short timeÆAir conditioner go to sleep and end test yourself procedure 2 Test yourself procedure of outdoor unit Force to run CN6 get through outdoor electrical board get to the test yourself procedureÆtest EEPROMÆtest temperature sensorÆtes...

Страница 31: ...ting protection of indoor coil while heating Te rise if Te 65 and it goes on for more than 5 s then it will stop working if 56 Te 65 the frequency of the compressor will decline in the rat e of 1Hz 3s Te decline if 52 Te 55 the compressor frequency remains unchanged if 48 Te 52 the frequency of the compressor will increase in the rate of 1Hz 30s When the compressor stop running over 3 min and Te 4...

Страница 32: ...DU module When IPDU breaks down any of the following vibration from the position speed detection of loop abnormal current sensor locking of the compressor damage of the compressor when the Case thermo moves the compressor stops operating and the outdo unit will display the fault code while the indoor unit will show l the total fault code and th compressor will re start again after 3 min If such fa...

Страница 33: ...mer Operation Sleep Operation Status O O normal operation regular shutdown O regular turn on O normal operation malfunction O O means go to sleep means at that stage of defrosting 3 Fault display A The three LED lights w e o s a ntil the fault disappear Digi Fault code Name of the troubleshooting environment temperature sensor ation failures of the indoor and outdoor unit d heating Digit Faul mper...

Страница 34: ... wind door will appear to full closing waving speed is 22 s 2 After turned on wind accordingly when heating it stops at diagram 1 position 5 while refrigerating it will return to diagram 1 position 2 3 wind door button on the remote control can be set to be free waving hand waving 4 when free waving w 5 waving scope for refrigerating is 50 diagram 1 between 2 and 4 waving speed is 5 when connected...

Страница 35: ...on operate as before press the sleeping button ten times within 8s with remote control towards controller if buzzer sounds twice canceling is ok if no sound for buzzer it fail to cancel 2 Content for memory function running model setting wind speed Ts waving status and turning on turning off status 3 If black out mode function is set successfully power is missing after turning off normally then co...

Страница 36: ...work rated frequency running will quit 2 Heating rated testing high wind and temperature 30 C are set receive signal for sleeping button 8 times continuously within 8s if refrigerating rated testing function is set successfully buzzer will sound four times system enter rated testing status compressor will run as fixed frequency 60Hz if any one condition above does not work rated frequency running ...

Страница 37: ...us that s set previous of refrigerating and heating high efficiency running when remote control quit run as the status that adjuster set 5 When there is protecting there will be no excessive high wind if frequency doesn t reach 80Hz excessive high wind is not allowed ...

Страница 38: ...t the filter from the right and left side 7 Screw off the bolts on the electrical box cover and unload the box cover 8 Screw off the 5 bolts for 1Hp AC or 8 bolts for 1 5Hp AC on the medium frame 9 Hold the both sides of the medium frame and open it gently 10 Turn up the medium frame by about 90 11 Offload the medium frame once hearing the crack sound 2 Electrical component 1 Do No 1 and 2 firstly...

Страница 39: ...ator 1 Do No 1 2 and 3 firstly 2 Offload the connecting pipe 3 Offload the tube clip at the rear 4 Screw off the bolts at the right and left side 5 Lift up the evaporator and draw it out from the indoor unit 5 Indoor fan Fan motor 1 Screw off one bolt from the motor cover and remove the motor cover 2 Offload the motor from the fan 3 Offload the fan from bearing 37 ...

Страница 40: ...board and offload the board Screw the six fastening bolts from the front panel and offload the front panel 4 Screw off the fastening bolts from the electrical assembly 5 Screw off the eight fastening bolts and offload the outer frame 2 Outdoor fan motor 1 Do No 1 firstly 2 Screw off the fastenings screws clockwise 3 Offload the fan 4 Screw off the four fastening bolts and offload the fan motor 5 S...

Страница 41: ...ning bolts 3 Weld off the inlet and outlet tube 4 Offload the condenser 4 Compressor 1 Do No 1 2 and 3 firstly 2 Open the cover of compressor release the connection cord 3 Weld off the inlet and outlet tube 4 Screw off the three screws 5 Offload the compressor 39 ...

Страница 42: ...Exploded Pictures 1 Indoor unit exploded picture ASW H09A4 SAR1DI 40 ...

Страница 43: ...e clamp 1 14 塑封电机 Indoor fan motor 3 15 滑块 Slip block 1 16 变压器 Transformer 1 17 电控盒 Electric controller box 1 18 端子板 Terminal board 1 19 压线板 Wire clamp 1 20 蒸发器配管 Evaporator tubing assembly 1 21 遥控器接收座 Signal receiver holder for remote controller 1 22 主控板 Main PCB 1 23 电控盒上盖 Cover of electric controller box 1 24 接线盖 Top cover of electric controller box 1 25 蒸发器 Evaporator 1 26 步进电机 Step motor 1 27...

Страница 44: ... 2 Outdoor unit exploded picture ASW H09A4 SAR1DI 42 ...

Страница 45: ... module and reactance element 1 19 散热片 Radiating fin 1 20 四位端子板 Four phase terminal board 1 21 电器架 A Electric board A 1 22 电器盖板 Handle 1 23 右侧板 Right side plate 1 24 隔风立板组件 Partition panel 1 25 四通阀线圈 Four way valve circuit 1 26 四通阀管路组件 Four way valve assembly 1 27 截止阀组件 B Liquid valve assembly 1 28 截止阀组件 A Gas valve assembly 1 29 阀板 Valve panel 1 30 压缩机消音棉 A Anti acoustic sponge A of compressor 1 ...

Страница 46: ... 3 Indoor unit exploded picture ASW H12A4 SAR1DI 44 ...

Страница 47: ...封电机 Indoor fan motor 1 13 电控盒 Electric controller box 1 14 变压器 Transformer 1 15 压线板 Wire clamp 1 16 端子板 Terminal board 1 17 遥控器接收座 Signal receiver holder for remote controller 1 18 蒸发器配管 Evaporator tubing assembly 1 19 蒸发器 Evaporator 1 20 主控板 Main PCB 1 21 电控盒上盖 Cover of electric controller box 1 22 接线盖 Top cover of electric controller box 1 23 接收窗 Receiver window for remote controller 1 24 电控盒盖 C...

Страница 48: ... 2 Outdoor unit exploded picture ASW H12A4 SAR1DI 46 ...

Страница 49: ... module and reactance element 1 19 散热片 Radiating fin 1 20 四位端子板 Four phase terminal board 1 21 电器架 A Electric board A 1 22 电器盖板 Handle 1 23 右侧板 Right side plate 1 24 隔风立板组件 Partition panel 1 25 四通阀线圈 Four way valve circuit 1 26 四通阀管路组件 Four way valve assembly 1 27 截止阀组件 B Liquid valve assembly 1 28 截止阀组件 A Gas valve assembly 1 29 阀板 Valve panel 1 30 压缩机消音棉 A Anti acoustic sponge A of compressor 1 ...

Страница 50: ...ADD NO 1166 North MingGuang Road AUX Technology Park Jiang Shan Town Ningbo Zhejiang P R China TEL 86 574 88220826 FAX 86 574 88220720 Http www cnaux com E mail auxsales mail auxgroup com ...