pipes is less than 25 .
2.
When the temperature of coiled pipe reaches less than 35
But more than 25 , The indoor fan will work under the
mode of “ mute". If the temperature of coiled pipe ascends
to 25 and then descends, it will stop working only when
the temperature is lowered to 22 .
3.
When the temperature of coiled pipe reaches more than 35
, the indoor fan will operate as set in the respect of wind
speed. If the temperature of coiled pipe ascends to 35
And then descends, it will enter into the operation mode of
“ mute" only when the temperature is lowered to 30 .
6.6.2 Afterheat-blowing function:
6.6.2.1 When the compressor stop working:
1.
When the temperature of coiled pipe is more than 35 , the indoor
fan will operate as set in respect of wind speed.
2.
When the temperature of coiled pipe is more than 25 , but less
than 35 , The indoor fan will operate under the mode of “ mute"
3.
When the temperature of coiled pipe is less than 25 , the indoor
fan will stop working.
6.6.2.2 The afterheat-blowing function when the air conditioner is just
shut down: If the temperature of indoor coiled pipe reaches more
than 30 , The indoor fan will operate under the mode of “ mute"; If
Содержание ASW-07B4/HSAR
Страница 1: ......
Страница 7: ...Operation Hints ...
Страница 8: ......
Страница 9: ......
Страница 33: ......
Страница 35: ...Chapter 5 Main Technical Data ...
Страница 42: ...4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...
Страница 61: ...Operation Hints ...
Страница 62: ......
Страница 63: ......
Страница 93: ...4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...
Страница 112: ...6 60 detachable cool warm type 70 detachable cool warm type ...
Страница 113: ...7 Operation Hints ...
Страница 114: ...8 ...
Страница 146: ...40 4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...