When the compressor is shut down, the outdoor fan and indoor fan
will stop working.
When T ring
≥
23
T set <T ring-1, the compressor will be working for 8 minutes and then
stopping for 3 minutes in cycles.
T set
≥
T ring-1, the compressor will be working for 3 minutes and then
stopping for 6 minutes in cycles.
And when T ring <23
T set
≤
T ring-1, the compressor will be working for 3 minutes and
then stopping for 4 minutes in cycles.
T set >T ring-1, the compressor will be working for 3 minutes and then
stopping for 6 minutes in cycles.
5.
Function of ventilation control
5.1 Under the mode of ventilation, the outdoor fan assembly will
always be shut down.
5.2 The indoor fan will operate as set in the respect of air quantity
without the gear- change of “high power".
5.3 The pendulum leaves will work according to the instructions sent
by remote control.
6.
Heating function
6.1 Under the mode of heating, the temperature range set is between 16
and 32 . And the temperature will be set by remote control.
Содержание ASW-07B4/HSAR
Страница 1: ......
Страница 7: ...Operation Hints ...
Страница 8: ......
Страница 9: ......
Страница 33: ......
Страница 35: ...Chapter 5 Main Technical Data ...
Страница 42: ...4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...
Страница 61: ...Operation Hints ...
Страница 62: ......
Страница 63: ......
Страница 93: ...4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...
Страница 112: ...6 60 detachable cool warm type 70 detachable cool warm type ...
Страница 113: ...7 Operation Hints ...
Страница 114: ...8 ...
Страница 146: ...40 4 To remove the axial flow fan and fan motor 5 To remove the electric assembly ...