Instructions, AutroFlame X33AFPL, 116-P-X33AFPL/IGB, rev . A, 2016-11-04
P/N 95-8750, v2 .4, rev . 1/16
Autronica Fire and Security AS
Page A-3
FM Approval and Performance Report – Continued
Very High Sensitivity
False Alarm Source
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response Time
(seconds)
Sunlight, direct, modulated, reflected
—
6-inch propane
6 (1 .8)
< 10
Vibration
N/A
3-inch propane
10 .5 (3 .2)
< 10
Radio frequency interference
1 (0 .3)
3-inch propane
12 (3 .7)
< 10
Arc welding, #7014
40 (12 .2)
1 x 1 foot n-Heptane
40 (12 .2)
4
6 kw heater, modulated
80 (24 .4)
1 x 1 foot n-Heptane
80 (24 .4)
2
6 kw heater, unmodulated
10 (3)
1 x 1 foot n-Heptane
80 (24 .4)
3
250 w vapor lamp, modulated
3 (0 .9)
1 x 1 foot n-Heptane
80 (24 .4)
2
300 w incandescent lamp, modulated
3 (0 .9)
1 x 1 foot n-Heptane
80 (24 .4)
7
500 w shielded quartz halogen lamp, modulated
8 (2 .4)
1 x 1 foot n-Heptane
80 (24 .4)
2
500 w unshielded quartz halogen lamp, modulated
8 (2 .4)
1 x 1 foot n-Heptane
80 (24 .4)
3
1500 w electric radiant heater, modulated
10 (3)
1 x 1 foot n-Heptane
80 (24 .4)
5
Two 34 w fluorescent lamps, modulated
3 (0 .9)
1 x 1 foot n-Heptane
80 (24 .4)
3
Medium Sensitivity
False Alarm Source
Distance
feet (m)
Fire Source
Distance
feet (m)
Average Response Time
(seconds)
Sunlight, direct, modulated, reflected
—
6-inch propane
6 (1 .8)
< 4
Vibration*
N/A
N/A
N/A
N/A
Radio frequency interference
1 (0 .3)
6-inch propane
6 (1 .8)
< 1
Arc welding, #7014
10 (3)
1 x 1 foot n-Heptane
40 (12 .2)
4
6 kw heater, modulated
60 (18 .3)
1 x 1 foot n-Heptane
60 (18 .3)
2
6 kw heater, unmodulated
10 (3)
1 x 1 foot n-Heptane
60 (18 .3)
2
250 w vapor lamp, modulated
3 (0 .9)
1 x 1 foot n-Heptane
60 (18 .3)
1
300 w incandescent lamp, modulated
3 (0 .9)
1 x 1 foot n-Heptane
60 (18 .3)
1
500 w shielded quartz halogen lamp, modulated
8 (2 .4)
1 x 1 foot n-Heptane
60 (18 .3)
1
500 w unshielded quartz halogen lamp, modulated
8 (2 .4)
1 x 1 foot n-Heptane
60 (18 .3)
1
1500 w electric radiant heater, modulated
10 (3)
1 x 1 foot n-Heptane
60 (18 .3)
6
Two 34 w fluorescent lamps, modulated
3 (0 .9)
1 x 1 foot n-Heptane
60 (18 .3)
2
* Fire was verified with very high sensitivity only .
A maximum delay of 1 second must be added to the average response time to account for the delay in communication of alarm from the detector
to the control panel .
RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES