background image

Instructions, AutroFlame X33AFPL, 116-P-X33AFPL/IGB, rev . A, 2016-11-04

P/N 95-8750, v2 .4, rev . 1/16

Autronica Fire and Security AS

Page A-3

FM Approval and Performance Report – Continued

Very High Sensitivity

False Alarm Source

Distance

feet (m)

Fire Source

Distance

feet (m)

Average Response Time

(seconds)

Sunlight, direct, modulated, reflected

6-inch propane

6 (1 .8)

< 10

Vibration

N/A

3-inch propane

10 .5 (3 .2)

< 10

Radio frequency interference

1 (0 .3)

3-inch propane

12 (3 .7)

< 10

Arc welding, #7014

40 (12 .2)

1 x 1 foot n-Heptane

40 (12 .2)

4

6 kw heater, modulated

80 (24 .4)

1 x 1 foot n-Heptane

80 (24 .4)

2

6 kw heater, unmodulated

10 (3)

1 x 1 foot n-Heptane

80 (24 .4)

3

250 w vapor lamp, modulated

3 (0 .9)

1 x 1 foot n-Heptane

80 (24 .4)

2

300 w incandescent lamp, modulated

3 (0 .9)

1 x 1 foot n-Heptane

80 (24 .4)

7

500 w shielded quartz halogen lamp, modulated

8 (2 .4)

1 x 1 foot n-Heptane

80 (24 .4)

2

500 w unshielded quartz halogen lamp, modulated

8 (2 .4)

1 x 1 foot n-Heptane

80 (24 .4)

3

1500 w electric radiant heater, modulated

10 (3)

1 x 1 foot n-Heptane

80 (24 .4)

5

Two 34 w fluorescent lamps, modulated

3 (0 .9)

1 x 1 foot n-Heptane

80 (24 .4)

3

Medium Sensitivity

False Alarm Source

Distance

feet (m)

Fire Source

Distance

feet (m)

Average Response Time

(seconds)

Sunlight, direct, modulated, reflected

6-inch propane

6 (1 .8)

< 4

Vibration*

N/A

N/A

N/A

N/A

Radio frequency interference

1 (0 .3)

6-inch propane

6 (1 .8)

< 1

Arc welding, #7014

10 (3)

1 x 1 foot n-Heptane

40 (12 .2)

4

6 kw heater, modulated

60 (18 .3)

1 x 1 foot n-Heptane

60 (18 .3)

2

6 kw heater, unmodulated

10 (3)

1 x 1 foot n-Heptane

60 (18 .3)

2

250 w vapor lamp, modulated

3 (0 .9)

1 x 1 foot n-Heptane

60 (18 .3)

1

300 w incandescent lamp, modulated

3 (0 .9)

1 x 1 foot n-Heptane

60 (18 .3)

1

500 w shielded quartz halogen lamp, modulated

8 (2 .4)

1 x 1 foot n-Heptane

60 (18 .3)

1

500 w unshielded quartz halogen lamp, modulated

8 (2 .4)

1 x 1 foot n-Heptane

60 (18 .3)

1

1500 w electric radiant heater, modulated

10 (3)

1 x 1 foot n-Heptane

60 (18 .3)

6

Two 34 w fluorescent lamps, modulated

3 (0 .9)

1 x 1 foot n-Heptane

60 (18 .3)

2

*   Fire was verified with very high sensitivity only .

A maximum delay of 1 second must be added to the average response time to account for the delay in  communication of alarm from the detector 
to the control panel .

RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES

Содержание AutroFlame X33AF PL

Страница 1: ...3AFPL IGB 2016 07 04 P N 95 8713 v1 1 rev 7 14 Instructions AutroFlame X33AF PL 116 P X33AFPL IGB 2016 07 04 P N 95 8713 v1 1 rev 7 14 Instructions AutroFlame X33AF PL 116 P X33AFPL IGB Rev A 2016 11 04 P N 95 8750 Instructions AutroFlame X33AF PL 116 P X33AFPL IGB Rev A 2016 07 15 P N 95 8750 v2 4 Rev 1 16 ...

Страница 2: ...sibility for any errors that may appear in the publication or for damages arising from the information in it No information in this publication should be regarded as a warranty made by Autronica Fire and Security The information in this publication may be updated without notice Product names mentioned in this publication may be trademarks They are used only for identification ...

Страница 3: ...TARTUP PROCEDURE 7 Fire Alarm Test 7 TROUBLESHOOTING 7 MAINTENANCE 8 Cleaning Procedure 8 oi plate Removal and replacement 8 X33AF PL Reflector Plates 9 Periodic Checkout Procedure 9 Clock Battery 9 FEATURES 9 SPECIFICATIONS 10 REPLACEMENT PARTS 11 Replacement parts 11 DEVICE REPAIR AND RETURN 11 Accessories 12 ORDERING INFORMATION 12 APPENDIX A FM APPROVAL AND PERFORMANCE REPORT A 1 APPENDIX B CS...

Страница 4: ......

Страница 5: ...es the detector capable of being powered and communicate with AutroSafe Integrated Fire and Gas panels IFG on the same pair of wire saving cable cost and weight Each detector has a built in short circuit isolator hence no detectors will be lost because of a single break or short circuit in the PowerLoop lines All alarms and faults will be signalled via PowerLoop The PowerLoop is a two wire power a...

Страница 6: ...ventive maintenance requirements These features can be performed at any time and eliminate the need for testing with a non calibrated external test lamp CAUTION These tests require disabling of all extinguishing devices to avoid release resulting from a successful test The Mag oi test is performed by placing a magnet at the location marked MAG OI on the outside of the detector see Figure 2 The Man...

Страница 7: ...application See Appendix A for third party approved fire test results Additional fire test results are available from Autronica IMPORTANT APPLICATION CONSIDERATIONS In applying any type of sensing device as a fire detector it is important to know of any conditions that can prevent the device from responding to fire and also to know what other sources besides fire can cause the device to respond We...

Страница 8: ...or handling electrostatic sensitive devices INSTALLATION NOTE The recommended lubricant for threads and O rings is a silicone free grease part number 116 005003 001 available from Autronica Under no circumstances should a lubricant containing silicone be used DETECTOR POSITIONING Detectors should be positioned to provide the best unobstructed view of the area to be protected The following factors ...

Страница 9: ...ure will not come in contact with the electrical connections or components of the system The integrity of the system regarding moisture protection must be maintained for proper operation and is the responsibility of the installer If conduit is used we recommend installing drains according to local codes at water collection points to automatically drain accumulated moisture It is also recommended t...

Страница 10: ...ring should be performed only by qualified personnel Detector Mounting Install the mounting arm assembly on a rigid surface The ideal installation surface should be free of vibration and suitable to receive 3 8 inch M10 bolts with a length of at least 1 inch 25 mm The surface must also have sufficient capacity to hold the detector and mounting arm weights See Specifications section Refer to the Q9...

Страница 11: ...he Maintenance section for complete information regarding cleaning of the detector viewing windows 3 Check input power to the unit 18 30V DC on terminals 1 3 and 15 18 ref fig 4 4 Check the fire panel display for fault status 5 Turn off the input power to the detector and check all wiring for continuity Important Disconnect wiring at the detector before checking system wiring for continuity 6 If a...

Страница 12: ... salt If a fault condition is still indicated after cleaning remove and clean the oi Plate Removal and Replacement procedure 3 In all environments clean all three viewing windows and reflector surfaces thoroughly Use a cotton swab and Autonicas window cleaning solution Use Isopropyl alcohol for contaminations that Autronicas window cleaning solution can not remove IMPORTANT When used in extreme en...

Страница 13: ...es Unequaled false alarm rejection Responds to a fire in the presence of modulated blackbody radiation i e heaters ovens turbines without false alarm Microprocessor controlled heated optics for increased resistance to moisture and ice Automatic manual or magnetic optical integrity oi testing Automatic alarm path test is performed once every 24 hours Easily replaceable oi plate FDT DMT capable Mult...

Страница 14: ...t cone of vision for methane fire detection 100 feet 30 5 m on and off axis on very high setting Refer to Appendix A for FM Approved cone of vision data RESPONSE TIME Typical response times are under 10 seconds Models are available that can respond to automotive paint gun fires in under 0 5 seconds See Appendix A for actual response times DIMENSIONS See Figure 6 ENCLOSURE MATERIAL Copper free alum...

Страница 15: ...1 Replacement oi Reflector Plates for X33AF PL with Black plate requires Inspector Connector to calibrate 116 010830 001 Replacement oi Reflector Plates for X33AF PL with Stainless Steel plate requires Inspector Connector to calibrate NOTE Refer to instruction manual 95 8530 to determine the correct oi replacement plate DEVICE REPAIR AND RETURN Prior to returning devices contact the nearest local ...

Страница 16: ...006097 001 Q1201 Laser 116 102871 001 Laser Battery 3V Lithium laser 116 007255 001 Q1201C1001 X Series Laser Holder AL Plastic 116 007338 001 Q2000A1001 X Series Weather Shield AL 116 007338 010 Q2033A10R X33AF X3302 FOV Limiter 10 AL 116 007338 020 Q2033A20R X33AF X3302 FOV Limiter 20 AL 116 007338 030 Q2033A30R X33AF X3302 FOV Limiter 30 AL 116 007912 010 Spare Restrictor Plate 10 AL 116 007912...

Страница 17: ...RIPTION X33AF Multispectrum IR Flame Detector TYPE MATERIAL A Aluminum S Stainless Steel 316 TYPE THREAD TYPE 4M 4 PORT METRIC M25 TYPE OUTPUTS 19 PowerLoop Protocol TYPE APPROVALS B INMETRO Brazil W FM CSA ATEX IECEx TYPE CLASSIFICATION 1 Division Zone Ex d e 2 Division Zone Ex d Type Approvals can use one or more letters to designate the approvals of the product ...

Страница 18: ...60 48 7 200 60 9 240 73 1 265 80 7 0 15 45 15 30 30 DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45 FROM HORIZONTAL 0 15 15 30 45 30 45 70 21 3 60 18 3 50 15 2 40 12 2 30 9 1 20 6 1 10 3 0 10 3 0 20 6 1 30 9 1 40 12 2 50 15 2 60 18 3 70 21 3 0 15 30 45 15 30 45 100 30 5 90 27 4 80 24 4 70 21 3 60 18 3 50 15 2 40 12 2 30 9 1 20 6 1 10 3 0 0 15 45 15 30 30 DETECTOR VERTICAL FIELD OF VIEW WITH DE...

Страница 19: ...in Feet m for Propane at Very High Sensitivity 32 inch plume 0 15 30 45 15 30 45 0 15 45 15 30 30 DETECTOR VERTICAL FIELD OF VIEW WITH DETECTOR AT 45 FROM HORIZONTAL 40 12 2 35 10 7 30 9 1 25 7 6 20 6 1 15 4 6 10 3 5 1 5 5 1 5 10 3 15 4 6 20 6 1 25 7 6 30 9 1 35 10 7 40 12 2 Field of View at Indicated Distance in Feet m for Methanol at Very High Sensitivity 6 in x 6 in 0 15 45 15 30 30 DETECTOR VE...

Страница 20: ...DETECTOR AT 45 FROM HORIZONTAL 10 3 20 6 1 30 9 1 40 12 2 50 15 2 60 18 3 70 21 3 80 24 4 90 27 4 100 30 5 125 38 1 Field of View at Indicated Distance in Feet m for Methane at Very High Sensitivity 32 inch plume Field of View at Indicated Distance in Feet m for JP 5 at Very High Sensitivity 2 x 2 feet 0 15 15 30 45 30 45 235 71 6 210 64 180 54 9 150 45 7 120 36 5 90 27 4 60 18 3 30 9 1 30 9 1 60 ...

Страница 21: ...5 at Medium Sensitivity 2 x 2 feet Field of View at Indicated Distance in Feet m for Propane at Medium Sensitivity 32 inch plume 0 15 30 45 15 30 45 100 30 5 90 27 4 80 24 4 70 21 3 60 18 3 50 15 2 40 12 2 30 9 1 20 6 1 10 3 0 15 15 30 45 30 45 70 21 3 60 18 3 50 15 2 40 12 2 30 9 1 20 6 1 10 3 Field of View at Indicated Distance in Feet m for Methanol at Medium Sensitivity 1 x 1 foot 0 15 15 30 4...

Страница 22: ...6 102740 002 Magnet 116 007739 001 Magnet and Extension Pole 116 010857 001 Q1130A1001 Flange Mount Assembly 116 007290 001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors 116 007290 002 Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only 116 011385 001 Q9033 Collar Attachment The following performance criteria were verified AUTOMATIC OPT...

Страница 23: ...st condition Pre burn from ignition Medium Sensitivity Fuel Size Distance feet m Average Response Time seconds n Heptane 1 x 1 foot 100 30 5 12 n Heptane 1 x 1 foot 50 15 2 2 Diesel 1 x 1 foot 70 21 3 4 Ethanol 1 x 1 foot 85 25 9 13 Methanol 1 x 1 foot 70 21 3 10 Methane 30 inch plume 65 19 8 3 Methane 30 inch plume 55 16 8 2 JP 5 2 x 2 feet 100 30 5 3 Office Paper 0 5 lb 19 x 19 x 8 50 15 2 6 Cor...

Страница 24: ...fluorescent lamps modulated 3 0 9 1 x 1 foot n Heptane 80 24 4 3 Medium Sensitivity False Alarm Source Distance feet m Fire Source Distance feet m Average Response Time seconds Sunlight direct modulated reflected 6 inch propane 6 1 8 4 Vibration N A N A N A N A Radio frequency interference 1 0 3 6 inch propane 6 1 8 1 Arc welding 7014 10 3 1 x 1 foot n Heptane 40 12 2 4 6 kw heater modulated 60 18...

Страница 25: ...x 1 foot n Heptane 50 15 2 14 Outdoor test conditions T Low Sensitivity False Alarm Source Distance feet m Fire Source Distance feet m Average Response Time seconds Sunlight direct unmodulated reflected 1 x 1 foot n Heptane 35 10 7 6 Sunlight direct modulated reflected 1 x 1 foot n Heptane 15 4 6 4 Arc welding steady 7014 5 1 5 1 x 1 foot n Heptane 50 15 2 10 Arc welding modulated 7014 5 1 5 1 x 1...

Страница 26: ...arm No alarm 300 w incandescent lamp 3 0 9 No alarm No alarm 500 w unshielded quartz halogen lamp 8 2 4 No alarm No alarm 500 w shielded quartz halogen lamp 3 0 9 No alarm No alarm 1500 w electric radiant heater 3 0 9 No alarm No alarm Two 34 w fluorescent lamps 3 0 9 No alarm No alarm T Low Sensitivity False Alarm Source Distance feet m Modulated Response Unmodulated Response Sunlight direct refl...

Страница 27: ... n Heptane 6 in x 6 in 80 24 4 45 45 5 6 45 30 4 4 Isopropanol 6 in x 6 in 70 21 3 45 45 5 5 45 30 4 6 Diesel 1 x 1 foot 100 30 5 45 45 2 3 45 30 4 3 Ethanol 1 x 1 foot 150 45 7 45 45 13 10 45 30 10 8 Methanol 6 in x 6 in 40 12 2 45 45 4 6 45 30 3 3 Methanol 1 x 1 foot 110 33 5 45 45 9 7 45 30 9 3 Methane 30 inch plume 100 30 5 45 45 7 3 45 30 2 2 JP 5 1 x 1 foot 100 30 5 45 45 2 4 45 30 3 2 JP 5 ...

Страница 28: ...5 13 7 45 45 3 3 45 30 7 1 JP 5 2 x 2 feet 90 27 4 45 45 4 2 45 30 2 2 Office Paper 0 5 lb 19 x 19 x 8 40 12 2 45 45 2 1 45 30 1 1 Corrugated Panel 18 x 36 40 12 2 45 45 2 1 45 30 1 1 Pre burn from ignition T Low Sensitivity Fuel Size Distance feet m Horizontal degrees Avg Horiz Response Time seconds Vertical degrees Avg Vert Response Time seconds n Heptane 1 x 1 foot 35 10 7 45 45 7 7 45 30 7 7 M...

Страница 29: ...lass I Division 2 Hazardous Locations ZONE CLASSIFICATION CLASS 4818 04 SIGNAL APPLIANCES Systems For Hazardous Locations Ex db eb IIC T6 T5 T6 Ta 50oC to 60oC T5 Ta 50oC to 75oC Ex tb IIIC T130oC Tamb 50oC to 75oC Seal required adjacent to enclosure IP66 Ex db IIC T6 T5 T6 Ta 55oC to 60oC T5 Ta 55oC to 75oC Seal required adjacent to enclosure IP66 IP67 APPLICABLE REQUIREMENTS CAN CSA C22 2 No 600...

Страница 30: ...he terminal compartment in type of explosion protection increased safety e They shall be IP66 IP67 rated suitable for the conditions of use and correctly installed Unused entries shall be closed with suitable certified blanking elements The metal housing for the Multispectrum infrared IR flame detector type X33AF PL must be electrically connected to earth ground For ambient temperatures below 10 C...

Страница 31: ...ns the X33AF PL Flame Detector must be electrically connected to earth ground The following accessories are ATEX approved for use with the X33AF PL Flame Detector Part Number Description 116 007290 001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors 116 007290 002 Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only 116 011385 001 Q9033 Co...

Страница 32: ... suitable certified blanking elements The metal housing for the Multispectrum infrared IR flame detector type X33AF PL must be electrically connected to earth ground For ambient temperatures below 10 C and above 60 C use field wiring suitable for both minimum and maximum ambient temperature Special conditions for safe use The front window assembly contains a special cemented joint construction In ...

Страница 33: ...L for use in Ships High Speed Light Craft and Offshore Applications Application Location Classes The following accessories are offshore approved to the listed approvals for use with the X33AF PL Flame Detector Part Number Description 116 102740 002 Magnet 116 007739 001 Magnet and Extension Pole 116 007290 001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detecto...

Страница 34: ... 4 rev 1 16 Autronica Fire and Security AS Page G 1 APPENDIX F ADDITIONAL APPROVALS BRAZIL UL BR 12 0093X Ex db eb IIC T6 T5 Ex tb IIIC T130 C T6 Tamb 50 C to 60 C T5 Tamb 50 C to 75 C IP66 OR Ex db IIC T6 T4 T6 Tamb 55 C to 60 C T5 Tamb 55 C to 75 C T4 Tamb 55 C to 125 C IP66 IP67 ...

Страница 35: ...l April 19 th 2016 2014 35 EU from April 20 th 2016 WEEE Directive 2002 96 EC Marine Equipment Directive 96 98 EC Certificate No MED B 9427 Certificate No MED D 1515 EN 60079 0 2012 A11 2013 EN 60079 1 2014 EN 60079 7 2015 EN 60079 31 2014 EN 60529 1991 A1 2000 A2 2013 EN 50130 4 2011 EN 61000 6 2 2005 EN 61000 6 4 2007 EN 61010 1 2010 Annex A 1 item No A 1 3 51 and Annex B Module B in the directi...

Страница 36: ...www autronicafire com ...