Instructions, AutroFlame X33AFPL, 116-P-X33AFPL/IGB, rev . A, 2016-11-04
P/N 95-8750 v2 .4, rev . 1/16
Autronica Fire and Security AS
Page 6
If disconnection of power is required, separate disconnect
capability must be provided .
WARNING
All entries must contain appropriately rated plugs
or fittings. It is required that each plug or fitting
be wrench-tightened to an appropriate installation
torque and meet the minimum thread engagement
requirements per the applicable local standards, codes,
and practices in order to retain the defined ratings,
PTFE sealant or equivalent should be used on NPT
threads.
IMPORTANT
Devices certified for hazardous locations shall be
installed in accordance with EN/IEC 60079-14 and NEC
505.
CAUTION
Installation of the detector and wiring should be
performed only by qualified personnel.
Detector Mounting
Install the mounting arm assembly on a rigid surface .
The ideal installation surface should be free of vibration
and suitable to receive 3/8 inch (M10) bolts with a length
of at least 1 inch (25 mm) . The surface must also have
sufficient capacity to hold the detector and mounting
arm weights (See "Specifications" section) . Refer to the
Q9033 Mounting Arm and Collar Attachment Manual (95-
8686) for additional mounting information . See Figure 3
for dimensions .
Connections
X33AF PL
1
3
18
15
In
Out
+
-
+
-
Figure 4 - If shielded cable is used for the PowerLoop, the shielding
should be continued .
13.1
(33.3)
10.6
(27.0)
4.0
(10.2)
4.0
(10.2)
3.0
(7.6)
3.0
(7.6)
4X ø0.42
(1.1)
F2069
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
Figure 3—Q9033 Mounting Bracket Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation .)