Instructions, AutroFlame X33AFPL, 116-P-X33AFPL/IGB, rev . A, 2016-11-04
P/N 95-8750 v2 .4, rev . 1/16
Autronica Fire and Security AS
Page 8
MAINTENANCE
IMPORTANT
Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.
WARNING
To avoid a potential electrostatic discharge (ESD),
the painted surface of the detector should only be
cleaned with a damp cloth.
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
To maintain maximum sensitivity and false alarm
resistance, the viewing windows of the X33AF PL must
be kept relatively clean . Refer to the procedure below for
cleaning instructions .
CLEANING PROCEDURE
CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
To clean the windows and
oi
plate, use Autronicas window
cleaner (part number 116-001680-001) and a soft cloth,
cotton swab or tissue and refer to the following procedure .
1. Disable any extinguishing equipment that is
connected to the unit.
2 . Since the X33AF PL is less affected by contamination
than other detectors, removal of the
oi
plate is needed
only under extreme conditions . In addition, it is not
necessary to achieve perfect cleanliness, because
IR is not significantly absorbed by slight films of oil
and/or salt . If a fault condition is still indicated after
cleaning, remove and clean the
oi
Plate Removal and
Replacement procedure .
3 . In all environments, clean all three viewing windows
and reflector surfaces thoroughly . Use a cotton
swab and Autonicas window cleaning solution . Use
Isopropyl alcohol for contaminations that Autronicas
window cleaning solution can not remove .
IMPORTANT
When used in extreme environments, the reflective
surface of the detector
oi
plate may eventually
deteriorate, resulting in reoccurring
oi
faults and
the need for
oi
plate replacement.
oi
PLATE REMOVAL AND REPLACEMENT
1 . Disable any extinguishing equipment that is connected
to the unit .
2 . Loosen the two captive screws, then grasp the
oi
plate by the visor and remove it from the detector . See
Figure 5 .
3 . Install the new (or cleaned)
oi
plate .
NOTE
When installing the stainless steel plate, ensure
that the gasket is present and correctly seated to
prevent moisture or contaminants from penetrating
behind the plate. To ensure even seating, tighten
both screws equally.
4 . Re-calibrate the detector's
oi
system . Refer to the
Inspector Monitor manual, number 95-8581, for
instructions regarding
oi
plate replacement and
oi
system recalibration .
CAUTION
Do not replace the
oi
reflector plate without also
recalibrating the
oi
system.
Recalibration of the
oi
system requires the use of the
Inspector Connector Cable and Inspector Monitor Software .
These two items are included in the
oi
replacement
kit, or they can be purchased separately . See Ordering
Information for details .
LOOSEN TWO CAPTIVE SCREWS
GRASP VISOR AND
REMOVE
oi
PLATE
B2106
Figure 5 –
oi
plate removal