Mounting Instructions
Technical Handbook, AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339, Revision 1, 2020-06-29,
Autronica Fire and Security
Page 51
9.2.5 Mounting onto a Conduit Box
The conduit box (part number 116-100001180 and 116-100001181)
has a total of six 20 or 25 mm knockouts; 2 at the bottom and 4
around the sides located at 90, 180, 270 and 360 degrees. A click-
type cable gland is included.
The use of cable glands provides an ingress protection level of IP55.
Mark and drill the necessary holes for the conduit box
Use a plier to gently remove the knockouts for the chosen cable
entries
Mount the conduit box to the ceiling by fastening the screws
Feed the cables through the chosen cable entries
Mount the protector base onto the conduit box by fastening the
screws