Technical Specifications
Technical Handbook, AutroGuard Multicriteria Protector Series V-430, V-530, V-100, V110 and V-120,
AutroGuard-Technical-Handbook, Doc-1004339, Revision 1, 2020-06-29,
Autronica Fire and Security
Page 28
Tone 7 - DIN tone 1200-500
High volume: 90 dB(A) @ 1 m max. / 77 dB(A) @ 1 m min.
Position
(degrees)
Horizontal plane dB(A) @ 1 m
Vertical plane dB(A) @ 1 m
Vmin
Vmax
Diff
Vmin
Vmax
Diff
15
78.34
79.44
1.1
82.04
83.44
1.4
45
78.94
79.64
0.7
81.84
83.34
1.5
75
89.24
90.44
1.2
78.14
79.64
1.5
105
84.74
85.54
0.8
81.44
82.54
1.1
135
77.04
78.64
1.6
81.04
82.34
1.3
165
79.94
80.94
1
83.34
84.94
1.6
Low volume: 82 dB(A) @ 1 m max. / 70 dB(A) @ 1 m min.
Position
(degrees)
Horizontal plane dB(A) @ 1 m
Vertical plane dB(A) @ 1 m
Vmin
Vmax
Diff
Vmin
Vmax
Diff
15
71.04
71.04
0
74.24
74.34
0.1
45
71.24
71.24
0
74.34
74.44
0.1
75
81.64
81.84
0.2
70.74
70.74
0
105
77.74
77.74
0
73.64
73.74
0.1
135
69.84
70.04
0.2
73.14
73.34
0.2
165
72.74
72.74
0
75.14
75.34
0.2
4.5 Integrated VAD
The following table provides an overview of the VAD intensity and
current consumption for each VAD intensity for white and red LED
indicators.
Technical specifications INTEGRATED VAD
VAD Color
VAD Intensity
Current
Consumption VAD
(LED indicator not
included)
Current
Consumption
alarm
indicator
Description
WHITE
High Intensity: C-3-12
20,0mA
2,1mA
At a given mounting height, the
Coverage Volume of a VAD is
defined by the diameter of the
coverage, given in meters.
Example:
C-3-12 corresponds to a ceiling-
mounted device giving a
coverage cylindrical volume of
12 m at 3 m height. For a white
VAD, high intensity is to be
configured.
Medium Intensity: C-3-9
12,7mA
2,1mA
Low Intensity: C-3-6
9,5mA
2,1mA
Open Class: O-2,5-4
(specified at 2,5m height)
3,8mA
2,1mA
RED*
High Intensity: C-3-8
18,7mA
2,1mA
Low Intensity: C-3-5
11,8mA
2,1mA
Open Class: O-2,5-4
(specified at 2,5m height)
7,5mA
2,1mA
*Available for V-430 only.