Page 34
14) Thread the cover switch cable, provided by installer, through the gland as shown in
Figure 21, below.
15) Connect the (2) conductors of the cable to the terminal labeled COVER CONTACT on
the bottom right side of the 863A Expansion Board. See Figure 22.
16) Reattach the RJ11 modular cable at J2 on the display board, previously released in
step 3, back to the J1 position on the main board. See Figure 17 on page 33.
CAUTION
: Do not connect the RJ11 cable to 863A Expansion Board.
Error! Reference source not found.
8.6.4
Bonding
The Digital Nano/Nano+ must also be connected to the pool/spa bonding system with an 8
AWG (6 AWG for Canada) wire. A bonding lug is provided at the bottom, exterior of the control
center. See below.
Cover Switch Cable
Bonding Lug
Directional Tab:
Position the tab forward in
relation to water flow.
Low Voltage Cable Connections
at Control Center
AC Input
Figure 21
Figure 22