I-50

SPC1 Series

 Specifications

 Features

Single-Phase, Power Controller   

● Various and simple input specification

• DC4-20mA, 1-5VDC, External 24VDC

• External adjuster (1kΩ)

• External contact (ON/OFF)

● Various function

• OUT ADJ (output limit) function

• 

SOFT START function (except for ON/OFF control method)

• OUT display function

• 50/60Hz automatic converting function

● Various control method by switch

• Phase control method

• Cycle control method (zero cross turn-on)

• ON/OFF control method (zero cross turn-on)

 Ordering Information

Rated load current

Marking language

Item

SPC

35

E

1

-

-

35

35A

50

50A

E

English

1

Single-phase

SPC

Solid state power controller

Control phase

Model

SPC1-35-E

SPC1-50-E

Power supply

220VAC

 50/60

Hz

Allowable voltage range

90 to 110% of rated voltage

Operating frequency fluctuation

±1Hz

Rated load current

35A (single-phase)

50A (single-phase)

Control power

220VAC

Control range

Phase control: 0 to 98%, Cycle control: 0 to 100%

Applied load

Resistance load (min. load: over 5% of rated current)

Cooling method

Natural cooling

Control circuit

Micom control type

Control input

• 1-5VDC

           • DC4-20mA (250Ω)       • ON/OFF (external relay contact or 24VDC

)

• External adjuster (1kΩ)          • Output limit input (front OUT ADJ. adjuster)     

Control 

method

By selection 

switch

• Phase control

1

• Cycle control (zero cross turn-on) - Period 0.5 sec, 2.0 sec, 10 sec 

1

• ON/OFF control (zero cross turn-on)

Starting type

SOFT START (0 to 50 sec variable) 

Indicator

Output indicator (OUT): red LED

Insulation resistance

Over 100MΩ (at 500VDC megger)

Dielectric strength

2000VAC 50/60Hz for 1minute

Noise immunity

±2kV the square wave noise (pulse width: 1us) by the noise simulator

Vibration

Mechanical

0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour

Malfunction

0.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 min

Shock

Mechanical

300m/s² (approx. 30G) in each X, Y, Z direction for 3 times

Malfunction

100m/s² (approx. 10G) in each X, Y, Z direction for 3 times

Environment

Ambient temp.

0 to 50

, storage: -25 to 65

Ambient humi.

35 to 85%RH, storage: 35 to 85%RH

Wire specification

AWG16 to 8

AWG8 to 6

Unit weight

Approx. 1kg

1:

 Refer to '

 

Operation and Function

'.

Environment resistance is rated at no freezing or condensation.

Please read “Safety considerations” in operation 

manual before using.

SPC1 Series

Содержание SPC1 Series

Страница 1: ... type Control input 1 5VDCᜡ DC4 20mA 250Ω ON OFF external relay contact or 24VDCᜡ External adjuster 1kΩ Output limit input front OUT ADJ adjuster Control method By selection switch Phase control 1 Cycle control zero cross turn on Period 0 5 sec 2 0 sec 10 sec 1 ON OFF control zero cross turn on Starting type SOFT START 0 to 50 sec variable Indicator Output indicator OUT red LED Insulation resistan...

Страница 2: ...l method This function must not be used in ON OFF control method It is available for all control methods OUT ADJ and SOFT START functions are not available in ON OFF control method Spacing When installing multiple power controllers please keep space at least 30mm in horizontal and 100mm in vertical between power controllers for heat radiation unit mm Connections 1 External connection 2 Connection ...

Страница 3: ...ntrol input After power is applied connecting the external adjuster 1 to and terminals and turning adjuster control from 0 to 100 It is available to control as OUT ADJ adjuster for the above 1 2 3 and set at 100 when it is not used 5 External 24VDC control input It can be used with external 24VDC voltage as below It is available to control of ON OFF outputs 100 for applying 24VDC and 0 for applyin...

Страница 4: ...rol fixed cycle Zero cross turn on It controls the power which is applied into the load to repeat ON OFF cycle like below picture with constant proportion according to control input signal It is easy to control the load and there is no ON OFF noise because it turns ON and OFF at the zero point of AC Usually it is used in a place or electric furnace which is not easily effected by external noise Eq...

Страница 5: ...ays as much as the value multiply of increased value and SOFT START set time When not using SOFT START function please make set value 0 This function must not be used in ON OFF control method OUT display This is LED lamp to display the status of output and will be getting brighter according as output 0 min LED light 100 max LED light 3 ON OFF control Zero cross This function is when control input ...

Страница 6: ...h are not used 9 The rapid fuse must be connected between R terminal and the power source 10 Do not use near the equipment which generates strong magnetic force or high frequency noise 11 This unit may be used in the following environments Indoors in the environment condition rated in Specifications Altitude max 2 000m Pollution degree 2 Installation category III E g 1 When controlling by limiting...

Отзывы: