background image

I-54

SPC1 Series

JP1

JP2

Cycle (sec)

SHORT

SHORT

0.5sec

SHORT

OPEN

2.0sec

OPEN

SHORT

10sec

OPEN

OPEN

× (not used)

To change control cycle, please change JP1 and JP2 of PCB as below.

 

OUT ADJ. (output limit) (0 to 100%)

This function will be [Control input (%) × OUT ADJ. (%) = 

Output] and it controls the power supplied into the load. 

Although control input is 100% (5V or 20mA), the output is 

the 50% which is proportioned with OUT ADJ. When not 

using OUT ADJ. function, please make set value 100%.

This function must not be used in ON/OFF control 

method.

 

SOFT START (0 to 50 sec) 

This function protects the load in cases that the set 

temperature is high, such as controlling the load (platinum. 

molybdenum, tungsten, infrared lamp, etc.) in which inrush 

current flows when power is supplied, or showing large 

width of temperature rise during initial operation.

SOFT START set time (T) is the required time that output 

reaches to 100%, and it is differentiated by OUT ADJ. 

set value. For example, SOFT START is set as 10sec 

and OUT ADJ. is set as 70%, it takes 7 sec to reach goal 

output. 

[Set time (T)×OUT ADJ. set value (%)=10 sec×0.7=7 sec] 

If increasing the OUT ADJ. before output reaches to 

goal output, it delays as much as the value, multiply of 

increased value (%) and SOFT START set time. When not 

using SOFT START function, please make set value 0.

This function must not be used in ON/OFF control 

method.

 OUT display

This is LED lamp to display the status of output and will be getting brighter according as output.

(0%: min. LED light, 100%: max. LED light)

3) ON/OFF control-Zero cross

This function is when control input is ON, output is 100%. 

When it is OFF, output is 0%.

It is the same function as SSR (Solid State Relay).

(It always turns ON/OFF at zero point of AC.)

OUT ADJ. and SOFT START function are not 

available in ON/OFF control method.

0%

T/2

T

50%

100%

< Output wave form of ON/OFF control >

<The output characteristic of OUT ADJ. and control input>

Control input

Control

input

Time

When OUT ADJ

is 50%

The output which

is applied into the

load is 50%

T: SOFT START setting time

T:  Time to get the output which is applied into the load is 

100%.

T/2:  Time to get the output which is applied into the load 

is 50%.

The output which

is applied into the

load is 100%

When OUT ADJ

is 100%

ON

Output

Output

Output

100%

100%

75%

50%

50%

0

25%

OFF

100%

0%

     SHORT

OPEN

When control input signal is 0% (DC4mA, 1VDC)

When control input signal is 25% (DC8mA, 2VDC)

T: Cycle (0.5sec)

 

T: Cycle (0.5sec)

When control input signal is 50% (DC12mA, 3VDC) When control input signal is 100% (DC20mA, 5VDC)

T: Cycle (0.5sec)

T: Cycle (0.5sec)

Содержание SPC1 Series

Страница 1: ... type Control input 1 5VDCᜡ DC4 20mA 250Ω ON OFF external relay contact or 24VDCᜡ External adjuster 1kΩ Output limit input front OUT ADJ adjuster Control method By selection switch Phase control 1 Cycle control zero cross turn on Period 0 5 sec 2 0 sec 10 sec 1 ON OFF control zero cross turn on Starting type SOFT START 0 to 50 sec variable Indicator Output indicator OUT red LED Insulation resistan...

Страница 2: ...l method This function must not be used in ON OFF control method It is available for all control methods OUT ADJ and SOFT START functions are not available in ON OFF control method Spacing When installing multiple power controllers please keep space at least 30mm in horizontal and 100mm in vertical between power controllers for heat radiation unit mm Connections 1 External connection 2 Connection ...

Страница 3: ...ntrol input After power is applied connecting the external adjuster 1 to and terminals and turning adjuster control from 0 to 100 It is available to control as OUT ADJ adjuster for the above 1 2 3 and set at 100 when it is not used 5 External 24VDC control input It can be used with external 24VDC voltage as below It is available to control of ON OFF outputs 100 for applying 24VDC and 0 for applyin...

Страница 4: ...rol fixed cycle Zero cross turn on It controls the power which is applied into the load to repeat ON OFF cycle like below picture with constant proportion according to control input signal It is easy to control the load and there is no ON OFF noise because it turns ON and OFF at the zero point of AC Usually it is used in a place or electric furnace which is not easily effected by external noise Eq...

Страница 5: ...ays as much as the value multiply of increased value and SOFT START set time When not using SOFT START function please make set value 0 This function must not be used in ON OFF control method OUT display This is LED lamp to display the status of output and will be getting brighter according as output 0 min LED light 100 max LED light 3 ON OFF control Zero cross This function is when control input ...

Страница 6: ...h are not used 9 The rapid fuse must be connected between R terminal and the power source 10 Do not use near the equipment which generates strong magnetic force or high frequency noise 11 This unit may be used in the following environments Indoors in the environment condition rated in Specifications Altitude max 2 000m Pollution degree 2 Installation category III E g 1 When controlling by limiting...

Отзывы: