10 Program Instructions
© Copyright Reserved Autonics Co., Ltd.
81
10.3
Program Control Instruction
10.3.1
JMP (Jump)
It jumps to the designated step (Step No.).
Instruction DATA
JMP
Instruction
Step No.
Step No.: Set the step number to jump. Setting range is 0 to 255.
When using JMP instruction, be sure to the position of END instruction.
At the loop between REP, RPE instruction, do not use JMP (Jump).
10.3.2
REP (Repeat Start)
It operates repeatedly for the set times from the next step of this instruciton to RPE (repeat
end instruction).
Instruction DATA
REP
Instruction
Repeat Count
Repeat Count
: Set the repeat times. Setting range is 1 to 255.
RPE (Repeat End) instruction should be below (higher step number) of the REP (Repeat Start)
instruction. The lower nested loops are available up to 3.