12. The Horizon Energy Monitoring System
With the New HT-400 Series
RS 485 Modbus
Communication
to enable full data
retrieval of kWh
for Graphic
analysis and Billing
COMMUNICATION SHIELD
MUST BE FITTED
COMMUNICATION SHIELD
MUST BE FITTED
Communications shield continuous
Belden 9841 or Equal Cable Screened
Twisted pair with full Coax shielding
for RS 485 Modbus connection.
Red..…TX+
,
Black…TX-
,
Green…Shield
to the next meter
B-
TX-
A+
TX+
Shield
Shield
B-
TX-
A+
TX+
Danger 415 Volts
Isolate electricity supply
before opening cover
The HC2-P is a surface mounted GPRS enabled data collection device capable of
storing information from up to 350 meters via 3 separate Lans
2 x Modbus – up to 127 meters on 1000 metres of Belden 9841 cable.
1 x M-bus – up to 100 devices on 1000 metres of Belcom 410P1824 cable.
HC2-P is powered from either the HS-PS7 or PS13
www.autometers.co.uk