Autometers Systems HORIZON HT-400 Скачать руководство пользователя страница 16

5.1.3 Energy Measurements

Imported/Exported active energy........           

Imported/Exported reactive energy.....    

Total active energy................                   

Total reactive energy............               

5.2 Measured Inputs

2 Voltage inputs through 4-way fixed connector with 25mm

2

 stranded wire capacity. single 

phase two wire (1 p2w), three phase three wire (3p3w) or three phase four wire (3p4w) 

unbalanced. Line frequency measured from L 1 voltage or L3 voltage. 

5.3 Interfaces for External Monitoring 

Three interfaces are provided:

RS 485 communication channel that can be programmed for Modbus RTU protocol

Pulse output 1 indicating real-time measured energy (configurable)

Pulse output 2 400imp/kWh (not configurable)

The Modbus configuration (baud rate etc.) and the pulse relay output assignments (kW/kVArh, 

import/export etc.) are configured through the set-up screens.

5.3.1 Pulse Output

The pulse output can be set to generate pulses to represent kWh or kVArh.

Rate can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh

0.1 = 100 Wh/VArh

1 = 1 kWh/kVArh

10 = 10 kWh/kVArh

100 = 100 kWh/kVArh

Pulse width 200/100/60 ms

Contact range 5-27V DC Max. current Input: 27mA DC

The test pulse output is a polarity dependent, passive transistor output requiring an external 

voltage source for correct operation. For this external voltage source, the voltage  (Ui) should 

be 5-27V DC, and the maximum input current (Imax) should be 27mA DC. To connect the 

impulse output, connect 5-27V DC to connector 7 (anode), and the signal wire(s) to connector 6 

(cathode). The meter pulse is indicated on the front panel.

Attention: Pulse output must be fed as shown in the wiring diagram above. Scrupulously 

respect polarities and the connection mode. Opto-coupler with potential-free SPST-NO contact.

5.3.2 RS485 Output for Modbus RTU 

For Modbus RTU, the following RS485 communication parameters can be configured from the 

set-up menu: 

Baud rate 2400, 4800, 9600, 19200, 38400 

Parity none / odd / even 

Stop bits 1 or 2 

RS485 network address nnn - 3-digit number, 001 to 247 

Please contact us if your require the Modbus/Mbus protocol document.

5.  Specification

5.1 Measured Parameters

The unit can monitor and display the following parameters of a single phase two wire(1p2w), 

three phase three wire(3p3w) or four phase four wire(3p4w) system.

 

5.1.1 Voltage and Current

Phase to neutral voltages 100 to 276V a.c. (not for 3p3w supplies). 

Voltages between phases 173 to 480V a.c. 

Percentage total voltage harmonic distortion (THD%) for each phase to N ( not for 3p3w supplies). 

Percentage voltage THD% between phases (three phase supplies only).  

Current THD% for each phase 

5.1.2 Power factor and Frequency and Maximum Demand

Frequency in Hz

Instantaneous power:

Power 0 to 96000 W

Reactive power 0 to 96000 VAr

Volt-amps 0 to 96000 VA

Maximum demanded power since last Demand reset Power factor

Maximum neutral demand current, since the last Demand reset (for three phase supplies only)

3 phase 4 wire

3 phase 3 wire

1 phase 2 wire

11.1 Mains/Load Connections

L1 L2 L3 N

L1 L2 L3 N

1

2

3

4

5

6

7

8

L1

L2

L3

L1

L2

L3

1

2

3

4

5

6

7

8

L1

N

L1

N

1

2

3

4

5

6

7

8

The HT-400 can be supplied with two wiring configurations: Mains entering at the top, load at 

the bottom - see fig.A; or mains entering at the bottom, load at the top - see fig.B.

MAINS

LOAD

Fig.A Mains at the top

11. Wiring Diagrams

WARNING

 

 

Important Safety Information is contained in sections 7-8. Familiarize yourself with this 

information before attempting installation or other procedures. Symbols used in this document:

Risk of Danger: These instructions contain important safety information. Read them before 

starting installation or servicing of the equipment.

Caution: Risk of Electric Shock

7. Maintenance

In normal use, little maintenance is needed. As appropriate for service conditions, isolate 

electrical power, inspect the unit and remove any dust or other foreign material present.  

Periodically check all connections for freedom from corrosion and screw tightness, particularly if 

vibration is present. 

The front of the case should be wiped with a dry cloth only. Use minimal pressure, especially 

over the viewing window area. If necessary wipe the rear case with a dry cloth. If a cleaning 

agent is necessary, isopropyl alcohol is the only recommended agent and should be used 

sparingly.  Water should not be used. If the rear case exterior or terminals should be 

contaminated accidentally with water, the unit must be returned to Autometers Systems Ltd for 

inspection and testing. 

8.  Installation

The meter is designed to be fitted on a DIN rail in a suitable enclosure. The unit is intended for 

use in a reasonably stable ambient temperature within the range -25°C to +55°C. Do not fit the 

meter where there is excessive vibration or in excessive direct sunlight.

Please note terminal covers should be fitted and sealed.  

See connection diagrams pages 14-15.

8.1 Safety

The unit is designed in accordance with IEC 61010-1:2010 – Permanently connected use, Normal 

condition. Installation category III, pollution degree 2, basic insulation for rated voltage. 

9. Electrician.

The HT-400 DIN rail meter should only be installed by a fully qualified electrician who has 

knowledge of electricity meters connected with current transformers.

It is the installer who is fully responsible for the safe installation of this meter. It must be 

installed to meet the current electrical regulations concerning installation of electricity meters. 

10.  EMC Installation Requirements

Whilst this unit complies with all relevant EU EMC (electro-magnetic compatibility) regulations, 

any additional precautions necessary to provide proper operation of this and adjacent 

equipment will be installation dependent and so the following can only be general guidance:

Avoid routing wiring to this unit alongside cables and products that are, or could be, a source of 

interference.

5.4 Accuracy

Voltage .......................................              

Current....................................... 

 

 

      

Frequency..................................

Power factor.............................. 

   

Active power (W)....................... 

 

      

Reactive power (VAr)................

Apparent power (VA)................ 

 

            

Active energy (Wh).................... 

 

            

Reactive energy (VARh)............ 

           

THD.............................................

Response time to step input... 

 

 

 

            

5.5 Reference Conditions of Influence Quantities

Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy 

is verified under nominal value (within the specified tolerance) of these conditions.

Ambient temperature.......................           

Input waveform.................................                 

Input waveform.................................       

5.6 Environment

Operating temperature............

Storage temperature................

Relative humidity.......................

Altitude.......................................

Warm up time............................

Vibration.....................................

Shock..........................................

* Maximum operating and storage temperatures are in the context of typical daily and seasonal 

variation.

5.7 Mechanics

DIN rail dimensions.............

Mounting..............................

Sealing...................................

Material.................................

6. Dimensions

The meter is a four module DIN rail mounted meter.

Dimensions are 72mm width x 100mm height x 66mm deep

The cut out hole for the front of the enclosure is 73mm x 

46mm

The auxiliary supply to the unit should not be subject to excessive interference. In some cases, a 

supply line filter may be required. 

To protect the product against incorrect operation or permanent damage, surge transients must 

be controlled. It is good EMC practice to suppress transients and surges at the source. The unit 

has been designed to automatically recover from typical transients; however in extreme 

circumstances it may be necessary to temporarily disconnect the auxiliary supply for a period of 

greater than 10 seconds to restore correct operation.

Screened communication leads are recommended and may be required. These and other 

connecting leads may require the fitting of RF suppression components, such as ferrite 

absorbers, line filters etc., if RF fields cause problems.

It is good practice to install sensitive electronic instruments that are performing critical functions 

in EMC enclosures that protect against electrical interference causing a disturbance in function.

www.autometers.co.uk

14

Содержание HORIZON HT-400

Страница 1: ...HORIZON SYSTEM METER HT 400 Multi Function Multi Tariff MID Approved Autometers Modbus V6 Energy Monitoring and Invoicing ...

Страница 2: ...terval Time 4 5 Backlit Set up 4 6 Supply System 4 7 Maximum Demand Reset 4 8 Change Password 5 Specification 5 1 Measured Parameters 5 1 1 Voltage and Current 5 1 2 Power Factor and Frequency and Maximum Demand 5 1 3 Energy Measurements 5 2 Measured Inputs 5 3 Interfaces for External Monitoring 5 3 1 Pulse Output 5 3 2 RS485 Output for Modbus RTU 5 4 Accuracy 5 5 Reference Conditions of Interface ...

Страница 3: ...er is supplied with an RS 485 Modbus protocol and 2 pulse outputs The Modbus output is defaulted to work directly with the Horizon data monitoring and invoicing system Declaration of Conformity We Autometers Systems Ltd 4B Albany Road Manchester M21 0AW UK ensure and declare that apparatus Energy Meter HT 400 with the measurement range 3x230 400V 0 5 10 100 A 50Hz are in conformity with the type a...

Страница 4: ...Phase 3 Wire and 3 Phase 4 Wire Two pulse output indicate real time energy measurement An RS485 output allows remote monitoring from another display or a computer 1 2 RS485 Serial Modbus RTU RS485 serial port with Mod bus RTU protocol to provide a means of remotely monitoring and controlling the Unit Set up screens are provided for setting up the RS485 port 1 3 Pulse output The HT 400 has two puls...

Страница 5: ...ect the Energy display screens In Set up mode this is the Enter Right or Confirm button Button V A ESC MD PF HZ P E 3 Keys and Displays Pulse indicator light Tariff indicator Phase and Neutral indicators Total indicator Clock indicating tariffs are programmed 1 4 Import and Export icons Digital numbers Pulse indicators Maximum Demand indicator Import indicator Export indicator Activation buttons Desc...

Страница 6: ...button selects a new range Phase to neutral voltages Current on each phase Phase to neutral voltage THD of 2nd to 19th Each phase Current THD of 2nd to 19th Frequency and Power Factor total Power Factor of each phase Maximum Power Demand Maximum Current Demand Instantaneous Active Power in kW Instantaneous Reactive Power in kVAr Instantaneous Volt Amps in KVA Total kW kVArh kVA V A ESC MD PF HZ P ...

Страница 7: ...active energy in kWh Date Year month day Factory programmed Time Hour minute second Example 00 02 16 Factory programmed Tariff 1 active energy Tariff 2 active energy Tariff 3 active energy Tariff 4 active energy T x run shows tariff running Imported reactive energy in kVArh Exported reactive energy in kVArh Setting up is password protected so you must enter the correct password default 1000 before proc...

Страница 8: ...Procedure 4 2 Communication Where the meter has been supplied with a RS 485 protocol output the individual parameters are set by using the front key panel 4 2 1 Modbus RS 485 Address Press button to enter the selection routine The current setting will be flashing V A ESC P MD PF HZ P MD PF HZ P 4 1 1 Menu Option Selection Use the and buttons to scroll through the different options of the set up menu...

Страница 9: ...rrent setting will flash From the set up menu use and buttons to select the Pulse Output option MD PF HZ P Press to enter the selection routine The unit symbol will flash E Use and buttons to choose kWh or kVArh On completion of the entry procedure press to confirm the setting and press to return to the main set up menu V A ESC MD PF HZ P E Use and buttons to choose Baud rate 2 4k 4 8k 9 6k 19 2k 38 ...

Страница 10: ...f the entry procedure press to confirm the setting and press to return to the main set up menu V A ESC MD PF HZ P E E From the set up menu use and buttons to select the DIT option The screen will show the currently selected integration time Press to enter the selection routine The current time interval will flash Use and buttons to select the time required Press to confirm the selection SET indicator...

Страница 11: ...to set the type of electrical system The meter provides a function to set the blue backlit lasting time 0 5 10 30 60 120 minutes Option 0 means the backlit always on here 4 5 Backlit Set up Press to enter the selection routine The dIt will flash Press to confirm the setting and press to return to the main set up menu Use and buttons to select the reset option 4 7 Maximum Demand Reset The meter provi...

Страница 12: ...5 1 1 Voltage and Current Phase to neutral voltages 100 to 276V a c not for 3p3w supplies Voltages between phases 173 to 480V a c Percentage total voltage harmonic distortion THD for each phase to N not for 3p3w supplies Percentage voltage THD between phases three phase supplies only Current THD for each phase 5 1 2 Power factor and Frequency and Maximum Demand Frequency in Hz Instantaneous power ...

Страница 13: ... kWh kVArh 100 100 kWh kVArh Pulse width 200 100 60 ms Contact range 5 27V DC Max current Input 27mA DC The test pulse output is a polarity dependent passive transistor output requiring an external voltage source for correct operation For this external voltage source the voltage Ui should be 5 27V DC and the maximum input current Imax should be 27mA DC To connect the impulse output connect 5 27V D...

Страница 14: ...typical daily and seasonal variation 5 7 Mechanics DIN rail dimensions Mounting Sealing Material 6 Dimensions The meter is a four module DIN rail mounted meter Dimensions are 72mm width x 100mm height x 66mm deep The cut out hole for the front of the enclosure is 73mm x 46mm 23 C 2 C 50 Hz MID 50 or 60Hz 2 non MID Sinusoidal distortion factor 0 005 25 C to 55 C 40 C to 70 C 0 to 95 non condensing ...

Страница 15: ...tion The meter is designed to be fitted on a DIN rail in a suitable enclosure The unit is intended for use in a reasonably stable ambient temperature within the range 25 C to 55 C Do not fit the meter where there is excessive vibration or in excessive direct sunlight Please note terminal covers should be fitted and sealed See connection diagrams pages 14 15 8 1 Safety The unit is designed in accordan...

Страница 16: ...surge transients must be controlled It is good EMC practice to suppress transients and surges at the source The unit has been designed to automatically recover from typical transients however in extreme circumstances it may be necessary to temporarily disconnect the auxiliary supply for a period of greater than 10 seconds to restore correct operation Screened communication leads are recommended an...

Страница 17: ...A TX 11 2 Communication Connections L1 L2 L3 N L1 L2 L3 N 1 2 3 4 5 6 7 8 L1 L2 L3 L1 L2 L3 1 2 3 4 5 6 7 8 L1 N L1 N 1 2 3 4 5 6 7 8 MAINS LOAD Fig B Mains at the bottom TX TX SH 1 2 B A The communications shield must be fitted before making the communication connections www autometers co uk 15 ...

Страница 18: ...oax shielding for RS 485 Modbus connection Red TX Black TX Green Shield to the next meter B TX A TX Shield Shield B TX A TX Danger 415 Volts Isolate electricity supply before opening cover The HC2 P is a surface mounted GPRS enabled data collection device capable of storing information from up to 350 meters via 3 separate Lans 2 x Modbus up to 127 meters on 1000 metres of Belden 9841 cable 1 x M b...

Страница 19: ...0 Series UE 1 UE 32 Autometers manufacture a number of metal enclosures compatible with the full range of meters it supplies The new UE 1 is the latest design for the range of panel meters The enclosure consists of a fuse and shorting terminal arrangement pre wired to the meter inside the enclosure The UE 32 enclosure can accommodate up to 16 meters ...

Страница 20: ...00 44 0161 861 9056 Fax 0161 881 3745 www autometers co uk Ref HT 400 07 2019 Product development is continuous and Autometers Systems Limited reserves the right to make alterations and manufacture without notice Products as delivered may therefor differ from the descriptions and illustrations in this publication ...

Отзывы: