background image

3

Sales 800-633-0405

www.productivity2000.com

.032A

2-Wire 4-20 mA

Transmitter

fuse

.032A

fuse

Note: Do not connect both ends of shield. 

I

+

I

+

COM

4-Wire 4-20 mA

Transmitter

Current Input Circuits

2-Wire Transmitter

4-Wire Transmitter

An Edison S500-32-R  0.032A fast-acting 

fuse is recommended for current loops.

+24VDC User 

Supplied Power 

+

+

User Supplied

Transmitter Power 

AC or DC

+

.032A

fuse

COM

I

+

3-Wire Current

Transmitter

3-Wire Transmitter

+

+24VDC User 

Supplied Power 

+ –

+ –

COM

Wiring Diagram

Schematic

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

ISOLATED

ANALOG

CIRCUIT

POWE R

CH11 ADC

CH15 ADC

CH12 ADC

CH16 ADC

COM

COM

COM

COM

I1+

I5+

I2+

I6+

I3+

I7+

I4+

I8+

+V

+V

-V

-V

I9+

I13+

I10+

I14+

I11+

I15+

I12+

I16+

CH9 ADC

CH13 ADC

CH10 ADC

CH14 ADC

CH3 ADC

CH7 ADC

CH4 ADC

CH8 ADC

CH1 ADC

CH5 ADC

CH2 ADC

CH6 ADC

+

ISOLATED ANALOG

CIRCUIT COMMON

INTERNAL

MODULE

CIRCUITRY

Содержание Productivity2000 P2-16ADL-1

Страница 1: ...ave any questions concerning the installation or operation of this equipment or if you need additional information please call Technical Support at 770 844 4200 This publication is based on informatio...

Страница 2: ...1010 2 201 Safety Input Specifications Input Channels 16 Module Signal Input Range 0 20 mA Signal Resolution 13 bit Resolution Value of LSB least significant bit 0 20 mA 2 44 A per count 1 LSB 1 count...

Страница 3: ...ower User Supplied Transmitter Power AC or DC 032A fuse COM I 3 Wire Current Transmitter 3 Wire Transmitter 24VDC User Supplied Power COM Wiring Diagram Schematic 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1...

Страница 4: ...your installation for use of this powerful feature 1 Align with slot 2 rotate to seated position Module Installation WARNING Do not apply field power until the following steps are completed See hot s...

Страница 5: ...24 1P ZL P2 CBL24 2P 3Accessories ZL RTB COM TW SD SL 1 TW SD MSL 1 Module Configuration Using the Hardware Configuration tool in the Productivity Suite programming software drag and drop the P2 16ADL...

Страница 6: ...2 3 4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Enter values for each breakpoint in the table Each breakpoint will define a segment of the non linear scaling 7 6 5 4 3 2 1...

Страница 7: ...7 Sales 800 633 0405 www productivity2000 com...

Страница 8: ...vision Date P2 16ADL 1 DS 2nd Ed Rev A 2 11 2022 Copyright 2015 AutomationDirect com Incorporated All Rights Reserved Worldwide Diagnostic Status Under Range Error 1 bit per channel Over Range Error 1...

Отзывы: