2
Tech Support 770-844-4200
www.productivity2000.com
General Specifications
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Altitude
2,000 meters max
Pollution Degree
2
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
1100mW maximum
Overvoltage Category
II
Enclosure Type
Open Equipment
Module Keying to Backplane Electronic
Module Location
Any I/O slot in a Productivity2000 System
Field Wiring
ZIPLink Wiring System ONLY. See “Wiring Options” on page 5.
Must use copper conductors 75°C or equivalent.
Terminal Type
24-pin Molex Style 43025-2400
Weight
100g (3.5 oz)
Agency Approvals
UL 61010-1 and UL 61010-2-201 File E139594, Canada & USA
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-201 Safety)*
Input Specifications
Input Channels
16
Module Signal Input Range
0–20 mA
Signal Resolution
13-bit
Resolution Value of LSB
(least significant bit)
0–20 mA = 2.44μA per count
( 1 LSB = 1 count)
Data Range
0–8191 counts
Input Type
Sinking, Single-ended (1 common)
Maximum Continuous Overload
±31mA
Input Impedance
124Ω, ±0.5% 1/2W Current Input
Filter Characteristics
Low Pass, -3dB @ 120Hz
Sample Duration Time
2ms per channel
(does not include ladder scan time)
All Channel Update Rate
25ms
Open Circuit Detection Time
Zero reading within 100ms
Conversion Method
Successive approximation
Accuracy vs. Temperature
±75PPM / ºC maximum
Maximum Inaccuracy
0.5% of range
(including temperature changes)
Linearity Error (end to end)
±0.036% of range
Monotonic with no missing codes
Input Stability and Repeatability
±0.024% of range
Full Scale Calibration Error
(including offset)
±0.097% of range
Offset Calibration Error
±0.097% of range
Max Crosstalk
4 counts / 0.048% of range
Recommended Fuse (external)
Edison S500-32-R, 0.032A fuse
External DC Power Required
24VDC (-20% / +25%) @ 35mA
*Meets EMC and Safety requirements. See the D.O.C. for details.