background image

2

Tech Support 770-844-4200

www.productivity2000.com

General Specifications

Operating Temperature

0º to 60ºC (32º to 140ºF)

Storage Temperature

-20º to 70ºC (-4º to 158ºF)

Humidity

5 to 95% (non-condensing)

Altitude

2,000 meters max

Pollution Degree

2

Environmental Air

No corrosive gases permitted

Vibration

IEC60068-2-6 (Test Fc)

Shock

IEC60068-2-27 (Test Ea)

Field to Logic Side Isolation

1800VAC applied for 1 second

Insulation Resistance

> 10MΩ @ 500VDC

Heat Dissipation

1200mW

Overvoltage Category

II

Enclosure Type

Open Equipment

Module Keying to Backplane Electronic
Module Location

Any I/O slot in a Productivity2000 System

Field Wiring

Use 

ZIP

Link Wiring System or removable terminal block (not 

included). See “Wiring Options” on page 5.

Connector Type (not included) 18-position removable terminal block
Weight

90g (3.2 oz)

Agency Approvals

UL 61010-1 and UL 61010-2-201 File E139594, Canada and USA
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-201 Safety)*

Input Specifications

Input Channel

4

Input Ranges

0–20 mA

Signal Resolution

16-bit

Resolution Value of LSB 

(least significant bit)

0–20 mA = 0.305 μA per count

 

(1 LSB = 1 count)

Data Range

0 to 65535 counts

Input Type

Sinking, Single-ended (1 common)

Maximum Continuous Overload

±31mA

Input Impedance

250Ω ±0.1% 1/4 W

Hardware Filter Characteristics

Low Pass, -3dB @ 100Hz

Sample Duration Time

9ms per channel 

(does not include ladder scan time)

All Channel Update Rate

80ms

Open Circuit Detection Time

Zero reading within 1s

Conversion Method

Successive approximation

Accuracy vs. Temperature

±25PPM / ºC maximum

Maximum Inaccuracy

0.1% of range 

(including temperature drift)

Linearity Error

±0.015% of range 

Monotonic with no missing codes

Input Stability and Repeatability

±0.015% of range (after 10 min warmup)

Maximum Full Scale Calibration Error

±0.015% of range maximum

Offset Calibration Error

±0.015% of range maximum

Maximum Crosstalk at DC, 50Hz and 60Hz -76dB, ±10 LSB
Recommended Fuse (external)

Edison S500-32-R, 0.032A fuse

External Power Supply Required

24VDC (-20% / +25%) 35mA

*Meets EMC and Safety requirements. See the D.O.C. for details.

Содержание Productivity2000 P2-04AD-1

Страница 1: ...ion is based on information that was available at the time it was printed At AutomationDirect com we constantly strive to improve our products and services so we reserve the right to make changes to the products and or publications at any time without notice and without any obligation This publication may also discuss features that may not be available in certain revisions of the product Removable...

Страница 2: ...61010 2 201 Safety Input Specifications Input Channel 4 Input Ranges 0 20 mA Signal Resolution 16 bit Resolution Value of LSB least significant bit 0 20 mA 0 305 μA per count 1 LSB 1 count Data Range 0 to 65535 counts Input Type Sinking Single ended 1 common Maximum Continuous Overload 31mA Input Impedance 250Ω 0 1 1 4 W Hardware Filter Characteristics Low Pass 3dB 100Hz Sample Duration Time 9ms p...

Страница 3: ...ng fuse is recommended for current loops 24VDC User Supplied Power User Supplied Transmitter Power AC or DC 032A fuse COM I 3 Wire Current Transmitter 3 Wire Transmitter 24VDC User Supplied Power COM I1 I2 I3 I4 COM COM 0V 24V 24 VDC User Supplied Power CH1 ADC CH2 ADC CH3 ADC CH4 ADC ISOLATED ANALOG CIRCUIT POWER ISOLATED ANALOG CIRCUIT COMMON INTERNAL MODULE CIRCUITRY COM COM COM COM COM COM 1 2...

Страница 4: ...n your installation for use of this powerful feature 1 Align with slot 2 rotate to seated position Module Installation WARNING Do not apply field power until the following steps are completed See hot swapping procedure for exceptions WIRESTRIP LENGTH WIRESTRIP LENGTH Step One Align module catch with base slot and rotate module into connector Locked Unlocked Step Two Pull top locking tab toward mod...

Страница 5: ... 1 module into the base configuration Module Configuration Wiring Options 1 ZIPLink Feed Through Modules and Cables 0 5 m 1 6 ft cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL RTB20 ZL RTB20 1 ZL P2 CBL18 ZL P2 CBL18 1 ZL P2 CBL18 2 Terminal Block with pigtail cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL P2 CBL18 1P ZL P2 CBL18 2P 3 Screw Terminal Block only P2 RTB Quantity 1 4 Spring Clamp Term...

Страница 6: ... 4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw input signal These values will relate to the minimum and maximum scaled values 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 The Scale Linear function can be used to Convert analog field input signals from the range which is native to the analog input module to an application specific range Mak...

Страница 7: ...2 04AD 1 Fw Rev 1 00 16 BIT 0 20mA 3 CH ENABLED DISPLAY UNITS MILIAMP 0 20mA These screens will then auto cycle Error Messages An existing error will be inserted into the cycling Status Info screen This screen will auto cycle with status information 1 00000 2 00000 3 00000 4 SPARE 1 0000H 2 0000H 3 0000H 4 SPARE 1 0 00mA 2 0 00mA 3 0 00mA 4 SPARE End of Status Menu List MISSING EXTERNAL 24VDC SELF...

Страница 8: ...ision Date P2 04AD 1 DS 1st Edition Rev A 2 11 2022 Copyright 2019 AutomationDirect com Incorporated All Rights Reserved Worldwide Diagnostic Status Under Range Error 1 bit per channel Over Range Error 1 bit per channel Module Failed 1 bit per module Missing 24V 1 bit per module ...

Отзывы: