background image

5

Sales 800-633-0405

www.productivity2000.com

P2-04AD-1

 

OH>?L

I1+
I2+
I3+
I4+

COM
COM
COM
COM
COM
COM

0V

24V+

COM

P2-04AD-1

    The “Under Range Error” bit for each 

channel activates for a signal around 

0mA ± offset error.

    The “Over Range Error” bit for each 

channel activates for a signal around 

19.999 mA ± gain error.

Using the Hardware Configuration tool in the 

Productivity Suite programming software, drag 

and drop the P2-04AD-1 module into the base 

configuration. 

  

Module Configuration

Wiring Options

 

1

ZIP

Link Feed Through 

Modules and Cables¹

0.5 m (1.6 ft) cable

1.0 m (3.3 ft) cable

2.0 m (6.6 ft) cable

ZL-RTB20
ZL-RTB20-1

ZL-P2-CBL18
ZL-P2-CBL18-1
ZL-P2-CBL18-2

       Terminal Block with pigtail cable

1.0 m (3.3 ft) cable

2.0 m (6.6 ft) cable

ZL-P2-CBL18-1P

ZL-P2-CBL18-2P

3

Screw Terminal Block only

P2-RTB
(Quantity 1)

4

Spring Clamp Terminal Block only

P2-RTB-1
(Quantity 1)

5

 

Accessories²

ZL-RTB-COM

TW-SD-SL-1

TW-SD-MSL-1

ZL-RTB20

ZL-RTB20-1

2

1.Cable + 

ZIP

Link Module = Complete System

2. ZL-RTB-COM provides a common connection point for power or ground

Содержание Productivity2000 P2-04AD-1

Страница 1: ...ion is based on information that was available at the time it was printed At AutomationDirect com we constantly strive to improve our products and services so we reserve the right to make changes to the products and or publications at any time without notice and without any obligation This publication may also discuss features that may not be available in certain revisions of the product Removable...

Страница 2: ...61010 2 201 Safety Input Specifications Input Channel 4 Input Ranges 0 20 mA Signal Resolution 16 bit Resolution Value of LSB least significant bit 0 20 mA 0 305 μA per count 1 LSB 1 count Data Range 0 to 65535 counts Input Type Sinking Single ended 1 common Maximum Continuous Overload 31mA Input Impedance 250Ω 0 1 1 4 W Hardware Filter Characteristics Low Pass 3dB 100Hz Sample Duration Time 9ms p...

Страница 3: ...ng fuse is recommended for current loops 24VDC User Supplied Power User Supplied Transmitter Power AC or DC 032A fuse COM I 3 Wire Current Transmitter 3 Wire Transmitter 24VDC User Supplied Power COM I1 I2 I3 I4 COM COM 0V 24V 24 VDC User Supplied Power CH1 ADC CH2 ADC CH3 ADC CH4 ADC ISOLATED ANALOG CIRCUIT POWER ISOLATED ANALOG CIRCUIT COMMON INTERNAL MODULE CIRCUITRY COM COM COM COM COM COM 1 2...

Страница 4: ...n your installation for use of this powerful feature 1 Align with slot 2 rotate to seated position Module Installation WARNING Do not apply field power until the following steps are completed See hot swapping procedure for exceptions WIRESTRIP LENGTH WIRESTRIP LENGTH Step One Align module catch with base slot and rotate module into connector Locked Unlocked Step Two Pull top locking tab toward mod...

Страница 5: ... 1 module into the base configuration Module Configuration Wiring Options 1 ZIPLink Feed Through Modules and Cables 0 5 m 1 6 ft cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL RTB20 ZL RTB20 1 ZL P2 CBL18 ZL P2 CBL18 1 ZL P2 CBL18 2 Terminal Block with pigtail cable 1 0 m 3 3 ft cable 2 0 m 6 6 ft cable ZL P2 CBL18 1P ZL P2 CBL18 2P 3 Screw Terminal Block only P2 RTB Quantity 1 4 Spring Clamp Term...

Страница 6: ... 4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw input signal These values will relate to the minimum and maximum scaled values 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 The Scale Linear function can be used to Convert analog field input signals from the range which is native to the analog input module to an application specific range Mak...

Страница 7: ...2 04AD 1 Fw Rev 1 00 16 BIT 0 20mA 3 CH ENABLED DISPLAY UNITS MILIAMP 0 20mA These screens will then auto cycle Error Messages An existing error will be inserted into the cycling Status Info screen This screen will auto cycle with status information 1 00000 2 00000 3 00000 4 SPARE 1 0000H 2 0000H 3 0000H 4 SPARE 1 0 00mA 2 0 00mA 3 0 00mA 4 SPARE End of Status Menu List MISSING EXTERNAL 24VDC SELF...

Страница 8: ...ision Date P2 04AD 1 DS 1st Edition Rev A 2 11 2022 Copyright 2019 AutomationDirect com Incorporated All Rights Reserved Worldwide Diagnostic Status Under Range Error 1 bit per channel Over Range Error 1 bit per channel Module Failed 1 bit per module Missing 24V 1 bit per module ...