4–19
Accel S-Curve
Default Setting: 00
Range: 00 to 07
This parameter is used whenever the motor and load need to be accelerated more
smoothly. The Accel S-Curve may be set from 0 to 7 to select the desired
acceleration S Curve.
Accel / Decel times 1 and 2 are applied to S-curve calculations.
S-curves can only be seen when the motor is loaded. Static testing will result in no
noticeable change on tuning software (i.e. GSoft).
Decel Time
1 or 2
Accel Time
1 or 2
S-curve
characteristics
Time
S-curve
characteristics
Time
Time
Time
Frequency
P 1.03 = 00
"Accel S curve Disabled"
P 1.04 = 00
"Decel S curve Disabled"
P1.03
Chapter 4: AC Drive Parameters
DURA
PULSE
AC Drive User Manual
1st Ed. Rev. D 05/2013
Содержание DURAPULSE GS3-2010
Страница 1: ...230V Class 1 50 Hp 460V Class 1 100 Hp User Manual AC Drive...
Страница 2: ......
Страница 6: ...w 4 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 8: ...Revision History DURAPULSE AC Drive User Manual h 2 BLANK PAGE...
Страница 68: ...Chapter 3 Keypad Operation and Quickstart 3 20 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 148: ...Chapter 4 AC Drive Parameters 4 80 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 151: ...5 1c Chapter 5 DURAPULSE MODBUS Communications DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 238: ...Chapter 6 Maintenance and Troubleshooting 6 10 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 241: ...DURAPULSE AC Drive User Manual A 1c Appendix A Accessories 1st Ed Rev D 05 2013...
Страница 292: ...Appendix A Accessories DURAPULSE AC Drive User Manual A 52 BLANK PAGE 1st Ed Rev D 05 2013...
Страница 314: ...Index i 8 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 315: ......
Страница 316: ......