4–17
Motor Line-to-Line Resistance R1
Default: 00
Range: 00 to 65535 milliohm
The motor auto detection feature will set this parameter. The user may also set
this parameter without using P0.05. Some motor manufacturers list this value on
the motor nameplate.
Motor No-Load Current
Default: Drive Rated Amps x 0.4
Range: Drive Rated Amps x 0.0 to 0.9 (Amps)
The rated current of the AC drive is regarded as 100%. The setting of the motor
no-load current will affect the slip compensation. The setting value must be less
than the Motor Rated Current (P0.01).
P0.07
P0.06
Chapter 4: AC Drive Parameters
DURA
PULSE
AC Drive User Manual
1st Ed. Rev. D 05/2013
Содержание DURAPULSE GS3-2010
Страница 1: ...230V Class 1 50 Hp 460V Class 1 100 Hp User Manual AC Drive...
Страница 2: ......
Страница 6: ...w 4 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 8: ...Revision History DURAPULSE AC Drive User Manual h 2 BLANK PAGE...
Страница 68: ...Chapter 3 Keypad Operation and Quickstart 3 20 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 148: ...Chapter 4 AC Drive Parameters 4 80 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 151: ...5 1c Chapter 5 DURAPULSE MODBUS Communications DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 238: ...Chapter 6 Maintenance and Troubleshooting 6 10 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 241: ...DURAPULSE AC Drive User Manual A 1c Appendix A Accessories 1st Ed Rev D 05 2013...
Страница 292: ...Appendix A Accessories DURAPULSE AC Drive User Manual A 52 BLANK PAGE 1st Ed Rev D 05 2013...
Страница 314: ...Index i 8 DURAPULSE AC Drive User Manual 1st Ed Rev D 05 2013...
Страница 315: ......
Страница 316: ......