Do-more T1H Series PLC User Manual, 1st Edition, Rev. C
7-5
Chapter 7: Specifications - Specialty I/O Modules
T1H-CTRIO Specifications
Input Specifications
Input
8 pts. sink / source
Maximum Input Frequency
100kHz
Minimum Pulse Width
5
e
sec
Input Voltage Range
9–30 VDC
Maximum Voltage
30VDC
Input Voltage Protection
Zener clamped at 33VDC
Rated Input Current
8mA typical, 12mA maximum
Minimum ON Voltage
9.0 VDC
Maximum OFF Voltage
2.0 VDC
Minimum ON Current
5.0 mA @ 9.0 VDC
Maximum OFF Current
2.0 mA
OFF to ON Response
Less than 3.0
e
sec
ON to OFF Response
Less than 3.0
e
sec
Output Specifications
Outputs
4 pts., (sink/source), independently isolated
Pulse Outputs
2 channels, 20Hz to 25kHz Pulse/Direction or
CW/CCW
Minimum Pulse Width
5
e
sec
Output Voltage Range
5–36 VDC
Maximum Output Voltage
36VDC
Maximum Load Current
1.0 A
Maximum Leakage Current
100
e
A
Inrush Current
5.0 A for 20ms
ON State V Drop
0.3 VDC or less
Overcurrent Protection
15A maximum
OFF to ON Response
Less than 3.0
e
sec
ON to OFF Response
Less than 3.0
e
sec
General Specifications
Discrete I/O Points Used
None (I/O map directly in T1H-DM1/E data
structure)
Base Power Required
400mA @ 5VDC
Isolation
2500V I/O to Logic, 1000V among Input Channels and All
Outputs
1A 1B 1C 1D
Y0 Y1
2A 2B 2C 2D
Y2 Y3
T1H-CTRIO
ERR CH1 CH2
OK