SIOL-EI8B-USER-M
47
Startup
Powered by
Version 1, May 2022
IO-Link port X0–X7 parameters
IO-Link Port X0–X7 Parameters
Byte
Parameters
Value
Default
value
Description
0
IO-Link Function Pin 4
◼
0 = Deactivated
◼
1 = IO-Link Manual Configuration
◼
2 = IO-Link Autostart
◼
3 = Digital Input NO
◼
4 = Digital Output
◼
97 =Digital Input NC
0
IO-Link function pin 4
1
Validation&Backup
◼
0 = No Device Check
◼
1 = Type Compatible Device V1.0
◼
2 = Type Compatible Device V1.1
◼
3 = Type Compatible Device V1.1,
Backup&Restore
◼
4 = Type Compatible Device V1.1, Restore
0
Validation and backup
* see footnote
2
Behavior Pin 2 (Ch1Y)
◼
0 = Automatic Mode (DIO)
◼
1 = Digital Input
◼
2 = Digital Output
◼
5 = AUX Power
◼
6 = Digital Input NC
◼
7 = Deactivated
0
Behavior Pin 2 (Ch1Y)
3
PortCycleTime
◼
0: As fast as possible
◼
1–255: Bit0–5 Multiplier / Bit6–7 TimeBase[ms]
0
Port cycle time
4–5
Vendor ID
◼
Vendor ID of the attached IO-Link device for
the use with validation setting
0
6–9
Device ID
◼
Device ID of the attached IO-Link device for the
use with validation setting
0
10
IO-Link Process Data Swap
◼
0 = No Swap
◼
1 = 16 Bit Swap
◼
2 = 32 Bit Swap
◼
3 = Full Swap
0
IO-Link process data exchange
11
IO-Link Event Integration
◼
0 = Standard Integration
◼
1 = Murrelektronik Integration
◼
2 = Murrelektronik IO-Link Extended Integration
0
IO-Link event integration
12
Digital Input Signal Filter Pin 4
◼
0 = No Filter
◼
1 = 1 ms
◼
2 = 3 ms
◼
3 = 5 ms
◼
4 = 10 ms
◼
5 = 15 ms
0
Digital input signal filter pin 4
13
Digital Input Signal Filter Pin 2
0
Digital input signal filter pin 2
14–15 Reserved
Fixed
0
Do not modify value
16
Digital Port Function Configuration
Pin 1
◼
0 = Deactivated
◼
1 = L+ (US) Sensor Supply
1
Digital port function configuration
pin 1
17–19 Reserved
Fixed
1
Do not modify value
20
Output Fault Recovery Mode Pin 2
◼
0 = Automatic Recovery
◼
1 = Manual Recovery
0
Output fault recovery mode pin 2
21
Output Fault Recovery Mode Pin 4
0
Output fault recovery mode pin 4
22
IO-Link Input Length
◼
0–32 bytes
0
IO-Link input length
23
IO-Link Output Length
◼
0–32 bytes
0
IO-Link output length
* When switching to the “Restore” state, any device configurations previously stored in the device are discarded, especially when switching
from “Backup&Restore” to “Restore”.
If a compatible device is connected for the first time in the “Restore” state, the master fetches the data storage data (one-time backup) from
the device, saves it and then sends this data to each newly connected, compatible device with a different configuration (restore).
NOTE
These parameters are repeated for each IO-Link port of the device.
NOTE
Data storage can only be implemented using the EDS file. Byte 0 “IO-Link Function Pin 4” must be
configured as “IO-Link Manual Configuration” for data storage settings to work correctly. See notes in
Section 3.2.1 for more details on data storage implementation.