SIOL-EI8B-USER-M
94
Powered by
Version 1, May 2022
Explanation of the process data
Appendix B: Explanation of the process data
NOTE
The addresses shown in the tables in Appendix B use 0-based addressing. The Productivity Suite soft
-
ware uses 1-based addressing. So, add 1 to any address in these tables when accessing these values in
Productivity Suite.
Digital Input
The order of the digital input data depends on the configuration parameter “Pin_Port_based_IO_Layout”.
This is explained in the following tables:
Port Based
Port-Based Digital Input
Byte
1
0
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Port
X7
X7
X6
X6
X5
X5
X4
X4
X3
X3
X2
X2
X1
X1
X0
X0
Pin
2
4
2
4
2
4
2
4
2
4
2
4
2
4
2
4
Channel
17
07
16
06
15
05
14
04
13
03
12
02
11
01
10
00
Pin Based
Pin-Based Digital Input
Byte
1
0
Bit
7
6
5
4
3
2
1
0
7
6
5
4
3
2
1
0
Port
X7
X6
X5
X4
X3
X2
X1
X0
X7
X6
X5
X4
X3
X2
X1
X0
Pin
2
2
2
2
2
2
2
2
4
4
4
4
4
4
4
4
Channel
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
NOTE
The tables for Port and Pin Based are also applicable to Digital Input Qualifier, Digital Output Qualifier
and Digital Output.
B.1. System Status
The system state bit string provides information about the entire device.
System Status Bit String
Byte
Description
0–3
Bit 0:
Bus/sensor supply undervoltage
Bit 1:
Actuator supply undervoltage Bit 3: External error
Bit 4:
At least one channel has a sensor short circuit
Bit 5:
At least one channel has an actuator short circuit
Bit 6:
At least one channel has an actuator warning
Bit 7:
At least one analog channel has an error
Bit 8:
Internal communication error
Bit 9:
At least one IO-Link channel has an error (except wire break)
Bit 10:
Bus/sensor supply overvoltage
Bit 11:
Actuator supply overvoltage
Bit 12:
At least one IO-Link channel has a wire break
Bit 13–31: Reserved, set to 0