SIOL-EI8B-USER-M
44
Startup
Powered by
Version 1, May 2022
7.4. Commissioning without EDS
NOTE
The byte addresses shown in the tables in Section 7.4 use 0-based addressing. The Productivity Suite
software uses 1-based addressing. So, add 1 to any address in these tables when accessing these values
in Productivity Suite.
7.4.1. Connections, parameters and properties
NOTE
Listen Only connections can only be established if there is already an established Multicast exclusive
owner connection.
7.4.2. Connection matrix
Exclusive Owner connection
Exclusive Owner Connection
Configuration assembly
Description
Input assembly
Output assembly
Instance
170
Length
384
Instance
Length
Instance
Length
E01
Digital IOs, IOL 32 bytes with status and diagnostics
101
394
111
260
Input Only connection
Input Only Connection
Configuration assembly
Description
Input assembly
Output assembly
Instance
170
Length
384
Instance
Length
Instance
Length
I01
Digital IOs, IOL 32 bytes with status and diagnostics
101
394
193
0
Listen Only connection
Listen Only Connection
Connection Names
Description
Input assembly
Output assembly
Instance
Length
Instance
Length
L01
Digital IOs, IOL 32 bytes with status and diagnostics
101
394
192
0
7.4.3. Assemblies
Sequence of configuration bytes
Assembly Instance 170
Instance
170
Total size in bytes
384
General
0–1
Diagnostic
2–19
IO-Link port X0
20–43
IO-Link port X1
44–67
IO-Link port X2
68–91
IO-Link port X3
92–115
IO-Link port X4
116–139
IO-Link port X5
140–163
IO-Link port X6
164–187
table continued on next page