background image

1 - 8 0 0 - 6 3 3 - 0 4 0 5

2

STRATUS TA20 Series Industrial Air Conditioners User Manual
1st Edition RevA. 

Stratus TA20 Series 

User Manual

Please include the Manual Number and the Manual Issue, both shown below,  
when communicating with Technical Support regarding this publication.

Manual Number: 

 

Stratus_TA20_UM_WMO_1ed

Issue: 

  1st 

Edition

Issue Date:  

 

12/16

Publication History

Issue

Date

Description of Changes

First Edition

12/16/2016

Original

Rev. A

05/24/2019

Unit Specifications Updated pg. 8 

Содержание Stratus TA20 Series

Страница 1: ...1 w w w a u t o m a t i o n d i r e c t c o m STRATUS TA20 Series Industrial Air Conditioners User Manual 1st edition RevA TA20 Series User Manual...

Страница 2: ...clude the Manual Number and the Manual Issue both shown below when communicating with Technical Support regarding this publication Manual Number Stratus_TA20_UM_WMO_1ed Issue 1st Edition Issue Date 12...

Страница 3: ...ox 6 Nameplate Information 6 Inspecting the Equipment 6 Basic Operation 7 Features 8 Unit Specifications 8 Preliminary Testing 10 Mounting the Air Conditioner 10 System Operation 11 System Faults 11 A...

Страница 4: ...en toute s curit Toute personne qui installe ou utilise cet quipement doit lire la pr sente publica tion et toutes les autres publications pertinentes avant de l installer ou de l utiliser Afin de r...

Страница 5: ...vailable weekdays from 9 00 a m to 6 00 p m Eastern Time We also encourage you to visit our web site where you can find technical and non technical information about our products and our company Visit...

Страница 6: ...he pallet not top side up other freight on top damaged or wet should be refused delivery Contact the shipper immediately upon discovery of shipping damage to schedule inspection by the freight company...

Страница 7: ...of 95 F plus the temperature differential of 5 F As the refrigerant pressure builds to a factory setpoint the condenser fan turns on to force air flow across the coils Refrigerant low pressure and hig...

Страница 8: ...ser inlet air filter Thermal expansion valve provides high performance over wide temperature range Internally insulated to minimize case heat loss Schrader valves on low AND high pressure service port...

Страница 9: ...26 4X 230 60 2 00 45 12 00 NEMA Type 4 Unit Specifications Model BTU H Max Ambient Temperature Standard Max Ambient Temperature Volts Hertz Running Amps Unit Weight lb Refrigerant Type Refrigerant Amt...

Страница 10: ...with the unit Using the template supplied determine where the air conditioner is to be mounted and make sure that all required cuts and holes will not interfere with or damage the enclosure There mus...

Страница 11: ...condition is indicated on the front panel and an alarm contact operates for remote alarming Three main conditions can shut down the AC compressor The condenser high temperature alarm The evaporator co...

Страница 12: ...t unit F Flashing Programming phase Digital Temperature Controller Overview The microprocessor based digital temperature controller performs the functions of controlling the enclosure temperature whil...

Страница 13: ...ey to display its value 3 Press the UP or DOWN arrow key to change its value 4 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds w...

Страница 14: ...fter initial 30 min delay Alarm relay operates HA2 Condenser high temperature P2 L 145 F for 3 minutes Alarm relay operates compressor off LA2 Condenser low temperature P2 l 50 F for 3 minutes Alarm r...

Страница 15: ...oil cleaning compounds and thorough back flush rinsing Refer to directions on the cleaning compounds selected Acid wash is not recommended as it reduces the life of the coil Note Do not use solvents t...

Страница 16: ...locked Installation must meet minimum clearance for condenser air flow Adjacent unit heating air Install baffle deflector or move unit s Perform touch test Compressor hot 190 F Suction accumulator col...

Страница 17: ...a u t o m a t i o n d i r e c t c o m STRATUS TA20 Series Industrial Air Conditioners User Manual 1st edition RevA Typical Frame Size TA20 0 1000 BTU H Units Dimensions All dimensions inches millimete...

Страница 18: ...5 18 STRATUS TA20 Series Industrial Air Conditioners User Manual 1st Edition RevA w w w a u t o m a t i o n d i r e c t c o m Typical Frame Size TA20 1 2000 BTU H Units Dimensions All dimensions inche...

Страница 19: ...RATUS TA20 Series Industrial Air Conditioners User Manual 1st edition RevA 1 8 0 0 6 3 3 0 4 0 5 Cutout for Typical Frame Size TA20 0 1000 BTU H Units Dimensions All dimensions inches millimeters Cuto...

Страница 20: ...1 8 0 0 6 3 3 0 4 0 5 20 STRATUS TA20 Series Industrial Air Conditioners User Manual 1st Edition RevA Schematic 1000 BTU 48VDC...

Страница 21: ...21 w w w a u t o m a t i o n d i r e c t c o m STRATUS TA20 Series Industrial Air Conditioners User Manual 1st edition RevA Schematic 1000 BTU 120V...

Страница 22: ...1 8 0 0 6 3 3 0 4 0 5 22 STRATUS TA20 Series Industrial Air Conditioners User Manual 1st Edition RevA Schematic 2000 BTU 120 240VAC...

Страница 23: ...cement Parts Wiring Terminal Blocks for Stratus Air Conditioners Manufacturer Manufacturer Part Description 2000 BTU Models Phoenix Contact 1718504 Plug Component Phoenix Contact 1716522 Feedthrough H...

Страница 24: ...1 8 0 0 6 3 3 0 4 0 5 24 STRATUS TA20 Series Industrial Air Conditioners User Manual 1st Edition RevA...

Отзывы: