DPM2 Process User Manual, 1st Edition
User Manual - DPM2 Series Process Panel Meters
10
Process Input Signal Wiring Diagrams (mA)
4 WIRE CONNECTION WITH EXTERNAL EXCITATION
4 WIRE CONNECTION WITH EXCITATION SUPPLIED BY THE DPM2
3 WIRE CONNECTION WITH EXTERNAL EXCITATION
3 WIRE CONNECTION WITH EXCITATION SUPPLIED BY THE DPM2
2 WIRE CONNECTION WITH EXTERNAL EXCITATION
2 WIRE CONNECTION WITH EXCITATION SUPPLIED BY THE DPM2
DPM2
TRANSDUCER
1
COM.
+mA
+OUT -OUT -EXC. +EXC.
0-20mA
4-20mA
5
EXC.
+
-
DPM2
TRANSDUCER
1
COM.
+mA
+OUT -OUT
+EXC.
0-20mA
4-20mA
5
EXC.
+
-
DPM2
TRANSDUCER
1
COM.
+mA
+OUT
+EXC.
4-20mA
5
EXC.
+
-
DPM2
TRANSDUCER
1
COM.
+mA
+OUT -OUT -EXC. +EXC.
0-20mA
4-20mA
5 6
+EXC.
DPM2
TRANSDUCER
1
COM.
+mA
+OUT -OUT
+EXC.
0-20mA
4-20mA
5 6
+EXC.
DPM2
TRANSDUCER
+mA
+OUT
+EXC.
4-20mA
5 6
+EXC.
Potentiometer Input Wiring Diagram (
Ω
)
DPM2
POTENTIOMETER
1
TERM.2
TERM.1
2
CENTER
(WIPER)
3
TERM.2
TERM.1
CENTER (WIPER)
NOTE:
Do not perform measurements with potentiometer subjected to external voltage, since it may
interfere in the measurement, alter the reading and even cause serious damages on this unit.