![Automation Direct ProSense DPM2 Series Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/automation-direct/prosense-dpm2-series/prosense-dpm2-series_user-manual_3021769007.webp)
DPM2 Process User Manual, 1st Edition
User Manual - DPM2 Series Process Panel Meters
7
Installation
To install the instrument, prepare a 92mm x 45mm
panel cut-out and slide the unit inwards making sure
to place the sealing gasket between the front side panel
and the front bezel.
While holding the unit in place, put the fixing clips on both sides of the case and slide them
through the guide tracks until they reach the panel at the rear side.
Press slightly to fasten the clips to the latching slots on the case and get the unit fully assembled
and close fitted to achieve a good seal.
To remove the instrument from the panel, pull the rear fixing clips latching tabs outwards until
they are disengaged, then slide the fixing clips back over the case.
Wiring Terminals
CN3
1 2
CN2
1 2 3 4 5 6 7
CN1
CN4
1
2
3
4
5
6
Output relay terminals
(DPM2-AT-2R-HL only)
Terminals
Connector
CN1
CN2
CN3 & CN4
Wire cross section
0.08 to 2.5mm² (28 to
12 AWG)
0.08 to 1.5mm² (28 to
14 AWG)
0.08 to 2.5mm² (28 to
12 AWG)
Strip length
8 to 9mm
6 to 7mm
8 to 9mm
Manufacturer
Wago 231-202/026-000 Wago 734-107
Wago 231-303/026-000
Cage clamp
connection
Insertion tool or
screwdriver with 0.5 mm
x 3.0 mm blade
Insertion tool or
screwdriver with 0.3 mm
x 1.8 mm blade
Insertion tool or
screwdriver with 0.5 mm
x 3.0 mm blade
Installation
Dimensions
96 x 48 x 83.1mm (1/8 DIN)
Panel Cutout
92 x 45mm
(Max. panel thickness 10mm)
Case Material
Polycarbonate UL 94 V-0