9 | Installation instructions
41
9.8
Cladding
The room-facing cladding (11) must be made of construction material class A1 non-flammable materi-
als. These are e.g. wall tiles, wall bricks, stove tiles, metal, plaster on lathing.
9.9
Fireplace aprons
The fireplace apron must not have any direct connection to the fireplace insert. It must be set up to be
self-supporting. The manufacturer offers various frames (23) for this purpose.
9.10 Ornamental beam
1 cm
1 cm
11
24
23
F
Fig. 14:
Ornamental beam
The ornamental beams (24) are permissible at a distance of
at least 1 cm in front of the cladding (11) and frame (23) of
the open fireplace insert if:
• the ornamental beam is not a component of the build-
ing.
• the clearance spaces to the cladding are so open that
no accumulation of heat can occur.
• the ornamental beam is not within the radiation area of
the open fireplace insert.
11 Cladding
23 Frame
24 Ornamental beam
F Expansion joint
9.11 Ceiling above the fireplace insert
G
8
11
Fig. 15:
Ceiling above fireplace insert
If the cavity above the fireplace insert reaches as far as the
room ceiling (8), then the latter must be protected if:
• it consists of flammable components
• it serves as a bearing component
The thermal insulation layer (11) (dimension G) must be ex-
ecuted in compliance with the normal regional installation
standards.
8 Room ceiling
11 Heat insulation layer
9.12 Floor in front of the fireplace insert
The floor in front of the fireplace insert must be made of flammable material. Minimum dimensions of
this non-flammable area: forward at least 50 cm, to the sides at least 30 cm.