www.austin-hughes.com
UM-X-800-XMS-02-S-Q420V1
P.22
Installation steps
Suggested
sensor position
- connect to the handle
- guide &
fi
x the cable with cable clips ( bundle with handle package )
- place the sensor at the top of the door, close to the hinge side
- adjust the sensor to ensure the sensing distance between door to
frame within 5mm while door in close status
- stick the re
fl
ective label on the rack frame just opposite to the sensor position
Sensor Operation
CLOSED
Rack
frame
Door
frame
Sensing distance
< 40 mm
Re
fl
ective label
Re
fl
ective label
OPENED
Sensing distance
> 50 mm
Rack
frame
Door
frame
DOOR CLOSE
- close door
- IR sensor detects the rack frame
- DOOR CLOSE SIGNAL sends out
DOOR OPEN
- open door
- IR sensor lose detection with rack frame
- DOOR OPEN SIGNAL sends out
sensing distance
door close : < 40mm
door open : > 50mm
sensing distance
door close : < 40mm
door open : > 50mm