Equipment Specifications
Case Material
Heavy duty welded uPVC
Connectors
Internal detachable Screw Terminal connectors accessed via
compression glands
Environmental
Storage Temperature range -20 to +70C, non condensing
Operating temperature range 0 to 50C. Internal heater option
available for use in conditions down to -25C
Power
100-240 VAC, 48 VAC, 45 to 60Hz or 11-30 VDC optional
Burden
40VA maximum
Sealing
IP65 all round, provided the display is mounted vertically and that all
cable glands and rear case-closure screws are properly secured.
Input Signals (bipolar)
0-10V, 0-5V, 1-5V, 0-10mA, 0-20mA, 4-20mA
Input Resistance
1 Megohm for voltage, 33 Ohms for current inputs
Accuracy
+/-0.05% of range
Span tempco
25 ppm/Degree Celsius
Zero Tempco
30 ppm/Degree Celsius
24V Excitation voltage
24VDC nominal rated at 60mA
10V Excitation voltage
10VDC nominal rated at 20mA
Filtering
/ smoothing
Selectable time constants of 0 to 25 seconds.
A/D conversion
Sigma-Delta 10 conversions per second, 50/60Hz rejection
Resolution 1 in 400 000 max. over full range
Display update rate
10 readings per second.
Display Range (max)
-199999 to +199999, depending on available signal level.
Plug-In Output Options
Analogue O/P
See analogue output manual for details.
Available from our website.
Alarm Relay O/P
See alarm output manual for details.
Available from our website.
ASCII Data O/P
See Serial output manual for details.
Available from our website.
Calendar/Clock option
See serial output manual for details.
Available from our website.