Logic input functions
The three contact closure inputs on the rear of the meter have default functions which are:-
Contact closure 1 = Tare
Contact closure 2 = Peak/Valley display
Contact closure 3 = Reset
You can re-assign these to include :HOLD, Nett/Gross value display, Memory page
address 1,2 or 4 (only if Multi-memory MEM option is installed)
Lockout Switch must be OFF
Press 3 seconds
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Press repeatedly until you see
CC.1
, followed by the existing function for
Contact Closure 1.
After you have set
CC.1
, you will get the
prompt
CC.2
to allow you to set Contact
Closure 2 function and when you have set
CC.2 you will get the prompt
CC.3
to allow
you to set Contact Closure 3 function
1
2
3
4
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Use UP or DOWN buttons to select from
these available functions...
tare
= Tare display to 0
PV
= Peak/Valley toggle
rst
= Reset
HoLd
= Freeze display
nt.gr
= Nett / Gross display
PA.1
= Page Address 1*
PA.2
= Page Address 2*
PA.4
= Page Address 4*
Set1
Set2
Output
Alarms
Digit
OK
Max/Min
Reset
Done!
!! This feature is available in Advanced Mode only !!
* Only available if the Multi-memory MEM option is installed
Defaults are:-
CC.1
=
tare
CC.2
=
PV
CC.3
=
rst
Press to accept