RESET of the regulator
Special situations
Unique features of AURATON T-1
Pressing the
RESET button
( ) causes the time and day setting to be erased, and the
regulator to be restarted.
•
When 3 consecutive transmissions (after 15 minutes) from the AURATON R25 RT regu
-
lator and/or the T-2 thermometer are lost, an error is signalled on the RT receiver (LED
flashing continuously red and green). The RT receiver starts executing the ON - OFF
cycle memorised during the last 24 hours of operation until the problem is removed.
•
When both signals return (from the AURATON R25 RT regulator and the T-2 thermom
-
eter), the error is cancelled and the receiver enters its normal mode of operation.
•
When only the T-2 thermometer signal returns, the receiver uses the last memorised
setpoint value and maintains it while signalling the error.
•
When the H-1 handles, the T-2 thermometer and the AURATON R25 RT regulator (the
temperature is measured with the T-2 thermometer) are paired with the receiver,
then maintaining the work cycle from the last 24 hours occurs only after losing the
signal from the T-2 thermometer. When only the signal from the AURATON R25 RT
is missing, the RT receiver automatically maintains the last memorised setpoint from
the AURATON R25 RT regulator and also signals an error.
•
When you have only the H-1 handles and the T-2 thermometer paired with the RT
receiver without the AURATON R25 RT regulator, the RT receiver maintains a constant,
factory-defined temperature of 20°C. If you pivot any window equipped with the H-1
handle paired with the receiver, a temperature of 17°C is maintained. If you open
any window equipped with the H-1 handle paired with the RT receiver, the receiver
switches off the heating device, but will switch it back on when the temperature falls
below 7°C.
•
A pre-installed lithium battery, provides an interrupted operation up to 20 years.
•
Switching the relay is synchronised with the wave of the 230 V mains voltage in order
to ensure that closing and opening contacts of the relay occurs around the zero-cross
-
ing point. This prevents the occurrence of an electric arc, significantly extending the
relay service time.
•
The AURATON RTH receiver is equipped with a unique algorithm for analysing the
ON - OFF cycles. The entire heating cycle from the last 24 hours is recorded in the
memory of the RTH receiver. In the event of losing communication with the AURA
-
TON T-1 RTH regulator and/or the T-2 thermometer, the RTH receiver automatically
executes the ON - OFF cycle memorised during the last 24 hours. This provides time
for restoring transmission (removing interferences) or fixing the T-1 regulator and/or
the T-2 thermometer without a significant deterioration of thermal comfort conditions
in the controlled spaces.