RWA Control Unit
LSF 7000
Connection of the Smoke Detector Technical Data
L1 IN
L1 OUT
L2
-R
L1 IN
L1 OUT
L2
-R
L1 IN
L1 OUT
L2
-R
22
1
LSF7000
10 kΩ
3
a
3b
3c
Smoke detector in the lift shaft
Mount the base of the smoke detector in a suitable place.
Connect the cables according to wiring diagram.
n
ote
If the LED in a smoke detector is lit, the au-
tomatic detector has triggered the alarm.
The activation is carried out via the “Close
Reset” button in an HSE button or via the
“Reset / EMERGENCY CLOSE” in the
Control Unit is reset. (see “Displays and
Operating Elements”).
LED Display on the Smoke Detector
Display
Status
red
light
- permanent
Alarm activation
red
blinking
- 1x per second
Check mode
yellow
blinking - every 4 seconds Fault
yellow
blinking - 1x per second
Standby mode tracking
Degree of contamination: 75 %
Important note for detector testing:
If the voltage of the detector line is interrupted by disconnecting and
reconnecting, or by pressing the reset button in the control panel,
the detectors react 4 minutes later by testing with test gas. The test
mode is indicated by the red flashing of the display. A yellow flashing
every 4 seconds indicates a fault in the detector (replace detector if
necessary).
= Smoke detector in shaft ceiling without console
= Smoke detector in shaft ceiling with console
= Smoke detector in shaft pit with console
3a
3b
3c
Smoke detection in lift shaft
View of the base
(without inserted detector)
10 kΩ Terminating resistor
in the last or only detector.
03
Insert a line terminating resistor in the last detector of a
line. Screw the detector insert into the base in a clockwise
direction until it engages.
Smoke detector with relay in base
Technical Data
Principle:
opt. Limit indicator
Voltage Range: 9 V ... 33 V DC
Closed Current Consumption: 30 mA ... 50 mA
Temperature Range: -20 °C ... + 60 °C
Air Humidity: :
0 % ... 90 %
Protection Rating: IP23D
VdS Recognition: G200017
Tested according to:
EN54-7
Description of the use of abbreviations:
L1 IN
= L1 Input
L1 OUT
= L1 Output
L2
= Common input and output terminal
-R
= MUST NOT BE OCCUPIED!!
Ø 100
50
Insert resistor
R
into
unused detector lines!
i
nDiviDual
C
omPonents
(D
esCriPtion
, P
rojeCt
P
lanning
, a
ssembly
)