MD2 slave address M0409
Baud rate M0343
Parity/stop bit M0782
Monitoring time M0781
Default values:
MD1 slave address
=
247
MD2 slave address
=
247
Baud rate
=
Auto
Parity/stop bit
=
Even, 1 stop bit
Monitoring time
=
15
seconds
Information
Parameter
MD2 slave address
is only available if AUMA redundancy I (option) is
available.
For further settings and information e.g. on redundancy, refer to Manual (Device
integration).
9.5.1.
Modbus TCP/IP gateway: set
Modbus TCP/IP gateway settings can be adapted by means of a web server.
Login password (default setting in the factory):
admin
Table 20: Default setting of the IP interface:
Static IP
Address Type
192.168.255.1
Static IP Address
255.255.0.0
Subnet Mask
192.168.0.1
Default Gateway
If required, only the IP interface must be adapted to the requirements of the Modbus
TCP/IP network. All further settings of the Modbus TCP/IP gateway (particularly the
port settings) are set as default in the factory.
9.6.
Test run
Only perform test run only once all settings previously described have been
performed.
9.6.1.
Direction of rotation at mechanical position indicator: check
Valve damage due to incorrect direction of rotation!
→
If the direction of rotation is wrong, switch off immediately (press STOP).
→
Eliminate cause, i.e. correct phase sequence for cable set wall bracket.
→
Repeat test run.
Information
Switch off before reaching the end position.
1.
Move actuator manually to intermediate position or to sufficient distance from
end position.
53