Select parameter
3.
Select parameter either:
→
click via the menu
to parameter, or
→
via direct display: press and enter ID
M0088
.
➥
Display indicates:
Trip torque CLOSE
CLOSE or OPEN
4.
Use
Up ▲ Down ▼
to select:
→
▶ Trip torque CLOSE
→
▶ Trip torque OPEN
➥
The black triangle
▶
indicates the current selection.
5.
Press
Ok
.
➥
Display shows the set value.
➥
The bottom row indicates:
Edit Esc
6.
Press
Edit
.
➥
Display indicates:
-
Specialist (4) →
continue with step 7
-
in bottom row
Up ▲ Down ▼ Esc →
continue with step 11
User login
7.
Use
Up ▲ Down ▼
to select user:
Information: Required user level:
Specialist (4)
or higher.
➥
The symbols have the following meanings:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
8.
Press
Ok
.
➥
Display indicates:
Password 0***
9.
Enter password (
→
enter password).
➥
Display shows the set value.
➥
The bottom row indicates:
Edit Esc
10. Press
Edit
.
Change value
11. Enter new value for tripping torque via
Up ▲ Down ▼
.
Information: The adjustable torque range is shown in round brackets.
12. Save new value via
Save
.
➥
The tripping torque is set.
13. Back to step 4 (CLOSED or OPEN): Press
Esc
.
Information
The following fault signals are issued if the torque setting performed has been reached
in mid-travel:
●
In the display of the local controls: Status indication
S0007 Fault
=
Torque fault OPEN
or
Torque fault CLOSE
The fault has to be acknowledged before the operation can be resumed. The
acknowledgement is made:
1.
either by an operation command in the opposite direction.
-
For
Torque fault OPEN
: Operation command in direction CLOSE
-
For
Torque fault CLOSE
: Operation command in direction OPEN
2.
or, in case the torque applied is lower than the preset tripping torque:
-
in selector switch position Local control (LOCAL) via push button RESET.
-
in selector switch position Remote control (REMOTE):
-
via the fieldbus, command reset., if the fieldbus is the active command
source.
-
via a digital input (I/O interface) with RESET command if a digital input
is configured for signal
RESET
and the I/O interface is the active
command source.
50
SQEx 05.2 – SQEx 14.2 / SQREx 05.2 – SQREx 14.2 Control unit: electronic (MWG)
Commissioning (basic settings)
ACExC 01.2 Non-Intrusive Modbus TCP/IP