For nominal voltage and 40 °C ambient temperature and an average load with 35 % of the maximum torque according to separate
technical data. The type of duty must not be exceeded.
1)
Technical data for handwheel activation switches
10
6
starts
Mechanical lifetime
Silver plated contacts:
12 V DC
U min.
250 V AC
U max.
3 A at 250 V (inductive load, cos phi = 0.8)
I max. AC current
3 A at 12 V (resistive load)
I max. DC current
12.2.
Features and functions of actuator controls
For mains voltage and mains frequency, refer to name plates at the controls and the motor
Permissible variation of the mains voltage: ±10 %
Permissible variation of the mains frequency: ±5 %
Option: Permissible variation of the mains voltage: ±30 %
Power supply
Mains frequency
24 V DC +20 % / –15 %
Current consumption: Basic version approx. 250 mA, with options up to 500 mA
The external power supply must have a reinforced insulation against the mains voltage in
accordance with IEC 61010-1 and may only be supplied by a circuit limited to 150 VA in ac-
cordance with IEC 61010-1.
External supply of the electron-
ics (option)
Current consumption of the controls depending on the mains voltage:
For permissible variation of mains voltage by ±10 %:
●
100 to 120 V AC = max. 740 mA
●
208 to 240 V AC = max. 400 mA
●
380 to 500 V AC = max. 250 mA
●
515 to 690 V AC = max. 200 mA
For permissible variation of mains voltage by ±30 %:
●
100 to 120 V AC = max. 1,200 mA
●
208 to 240 V AC = max. 750 mA
●
380 to 500 V AC = max. 400 mA
●
515 to 690 V AC = max. 400 mA
Motor current consumption: Refer to motor name plate
Current consumption
Category III according to IEC 60364-4-443
Overvoltage category
The controls are designed for the rated motor power, refer to motor name plate
Rated power
Standard:
Reversing contactors (mechanically and electrically interlocked) for motor power up to power
class A1
Options:
●
Thyristor unit for mains voltage up to 500 V AC (recommended for modulating actuators)
for AUMA power class B1
Switchgear
1) 2)
Standard:
Via digital inputs OPEN, STOP, CLOSE, EMERGENCY (via opto-isolator, OPEN, STOP,
CLOSE with one common), respect minimum pulse duration for modulating actuators
Option:
Additional enable inputs for directions OPEN and CLOSE
Control
Standard:
24 V DC, current consumption: approx. 10 mA per input
Options:
48 V DC, current consumption: approx. 7 mA per input
60 V DC, current consumption: approx. 9 mA per input
110 V DC, current consumption: approx. 8 mA per input
115 V DC, current consumption: approx. 15 mA per input
115 V AC, current consumption: approx. 15 mA per input
Voltage and current values for
control inputs
3)
58
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2 Control unit: electronic (MWG)
Technical data