10.
Corrective action
10.1.
Faults during commissioning
Table 9: Faults during commissioning
Remedy
Possible causes
Fault description
Set gear stage of the reduction gearing.
The control unit might have to be exchanged.
Reduction gearing is not suitable for
turns/stroke of the actuator.
Mechanical position indicator
cannot be set.
Determine overrun: Overrun = travel covered
from switching off until complete standstill.
Set limit switching again considering the
overrun (turn handwheel back by the amount
of the overrun).
The overrun was not considered when setting
the limit switching.
The overrun is generated by the inertia of
both the actuator and the valve and the delay
time of the controls.
Fault in end position
Actuator runs to end stop al-
though the limit switches work
properly.
10.2.
Fault indications and warning indications
Faults interrupt or prevent the electrical actuator operation. In the event of a fault,
the display backlight is red.
Warnings have no influence on the electrical actuator operation. They only serve
for information purposes.
Collective signals include further indications which can be displayed via the
Details
push button.
Table 10: Faults and warnings via status indications in the display
For indicated value > 0:
Description/cause
Indication on display
Press push button
Details
.
For details, refer to <Warnings and Out of
specification> table.
Collective signal 02:
Indicates the number of active warnings.
Warnings S0005
Press push button
Details
.
For details, refer to <Not ready REMOTE and
Function check> table.
Collective signal 04:
Indicates the number of active signals.
Not ready REMOTE S0006
Press push button
Details
to display a list
of detailed indications.
For details, refer to <Faults and Failure> table.
Collective signal 03:
Indicates the number of active faults.
The actuator cannot be operated.
Fault S0007
Press push button
Details
.
For details refer to <Warnings and Out of
specification> table.
Collective signal 07:
Indication according to NAMUR recommenda-
tion NE 107
Actuator is operated outside the normal oper-
ation conditions.
Out of specification S0008
Press push button
Details
.
For details, refer to <Not ready REMOTE and
Function check> table.
Collective signal 08:
Indication according to NAMUR recommenda-
tion NE 107
The actuator is being worked on; output sig-
nals are temporarily invalid.
Function check S0009
Press push button
Details
to display a list
of detailed indications.
Collective signal 09:
Indication according to NAMUR recommenda-
tion NE 107
Recommendation to perform maintenance.
Maintenance required S0010
Press push button
Details
to display a list
of detailed indications.
For details, refer to <Faults and Failure> table.
Collective signal 10:
Indication according to NAMUR recommenda-
tion NE 107
Actuator function failure, output signals are
invalid
Failure S0011
Table 11: Warnings and Out of specification
Remedy
Description/cause
Indication on display
Press push button
Details
to display a list
of individual indications.
Collective signal 06:
Possible cause:
Configuration setting is incorrect.
The device can still be operated with restric-
tions.
Config. warning
49
SQ 05.2 – SQ 14.2/SQR 05.2 – SQR 14.2 Control unit: electronic (MWG)
AC 01.2 Non-Intrusive
Corrective action