16.2 Operation mode LOCAL
Set selector switch (figure P3) on the local con-
trols to position LOCAL.
.
The actuator can be controlled by the push
buttons OPEN - STOP - CLOSE
(figure P1).
.
A change-over between push-tu-run
operation and self-retaining is possible (page
.
Faults (refer to pages 25, 26) and warnings
without automatic Reset must be confirmed
with the push button "Reset".
16.3 Operation mode REMOTE
Set selector switch (figure P4) on the local con-
trols to position REMOTE.
.
The actuator is controlled by external
REMOTE commands OPEN, STOP, CLOSE.
.
A change-over between push-to-run
operation and self-retaining (page 55,
subclause 16.10) is possible.
16.4 Operation mode EMERGENCY
The actuator can be brought to a programmed EMERGENCY position by
removal of the signal EMERGENCY (see wiring diagram
ACP ... KMS TP ...).
As the signal EMERGENCY works active-low, 24 V must be supplied to
contact X
K
Pin 1 in the normal state. An emergency operation is performed
when the signal is interrupted.
.
An EMERGENCY operation is performed either in selector switch position
LOCAL or REMOTE or only in REMOTE (parameter "
EMERGENCY
MODE
", page 32)
.
No emergency operation is performed when the selector switch is in
position OFF.
The operation mode EMERGENCY has the highest priority.
EMERGENCY operation behaviour:
(Parameter "
EMERGENCY BEHAVIOUR
", page 32)
Simple EMERGENCY operation behaviour "
GOOD SIGNAL FIRST
":
An EMERGENCY operation is only triggered when the EMERGENCY signal
at the EMERGENCY input falls from 24 V to 0 V, i.e. only if a 24 V signal
was previously connected to the EMERGENCY input.
52
Part-turn actuators SG 03.3 – SG 04.3
with AUMATIC AC 01.1
Operation instructions
Fig. P3
Fig. P4