32
Part-turn actuators SG 03.3 – SG 04.3
with AUMATIC AC 01.1
Operation instructions
Subgroup
Parameter
name
Sub-
menu
Standard
value
Min/M
ax
Valuetext
Note
M14
I/O 1
OUTPUT CONTACT
1
M14X2
2
36
LOSS OF PHASE
One phase is missing
37
I/O1 ANALOG
IN2 LOSS
Signal interruption of the parallel
interface analogue input 2
38
I/O1 ANALOG
IN1 LOSS
Signal interruption of the parallel
interface analogue input 1
OUTPUT CONTACT
2
M14X3
1
0-38
see output contact 1
OUTPUT CONTACT
3
M14X4
21
0-38
OUTPUT CONTACT
4
M14X5
11
0-38
OUTPUT CONTACT
5
M14X6
12
0-38
M15
FAILURE
MODE
FAILURE BEHA-
VIOUR
M15X0
0
0
OFF
Failure mode is switched off
1
GOOD SIGNAL
FIRST
See page 53, subclause 16.5
2
FAIL IMMEDIATE
DELAY TIME
M15X1
3.0
0
Delay time (in s)
see page 53, subclause 16.5
1200.0
FAILURE
POSITION
M15X2
0
0
FAIL AS IS
Behaviour of the actuator in case
of a failure (see page 53)
1
FAIL CLOSE
2
FAIL OPEN
3
FAIL TO PRESET
PRESET
POSITION
M15X3
0
0
Position (in percent) at which the
actuator stops
100.0
FAILURE
SOURCE
M15X4
1
0
SETPOINT E1
Failure source
1
E1 OR E2
FEEDBACK
2
BUS INTERFACE
Only with bus interface
M16
EMERGENCY
MODE
EMERGENCY
BEHAVIOUR
M16X0
0
0
OFF
Emergency operation is switched
off
1
GOOD SIGNAL
FIRST
see page 52, subclause16.4
2
ACTIVE IMME-
DIATE
EMERGENCY
POSITION
M16X1
0
0
FAIL AS IS
Behaviour of the actuator in case
of an emergency operation (see
page 53)
1
FAIL CLOSE
2
FAIL OPEN
3
FAIL TO PRESET
EMERG. SEL.
M16X2
0
0
REMOTE ONLY
Emergency operation only from
REMOTE or also from LOCAL
1
REMOTE AND
LOCAL
EMERGENCY
BY-PASS
M16X3
0
0
NONE
No by-pass
1
THERMAL
Thermo signal (motor protection)
by-passed (see also page 53)