5.2.3.
Terminal compartment : close
Figure 18: Close terminal compartment
[1-A] Cover (SH version)
[1-B] Cover (SB version)
[2]
Screws for cover
[3]
O-ring
[4]
Screws for socket carrier
[5]
Socket carrier
[6]
Blanking plug
[7]
Cable gland (not included in delivery)
[8]
DBE resistant cable entry (option)
Short-circuit due to pinching of cables!
Risk of electric shock and functional failures.
→
Carefully fit socket carrier to avoid pinching the cables.
SH/SB version
1.
Insert the socket carrier [5] into the cover [1] and fasten with screws [4].
2.
Clean sealing faces of cover [1] and housing.
3.
Check whether O-ring [3] is in good condition, replace if damaged.
4.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5.
Fit cover [1] and fasten screws [2] evenly crosswise.
6.
Fasten cable glands and blanking plugs applying the specified torque to ensure
the required enclosure protection.
23
SAI 07.2 – SAI 16.2 / SARI 07.2 – SARI 16.2
for use in nuclear power plants
Electrical connection