9.
Connect signal cables in push-in technology according to order-related wiring
diagram.
Information: Only required if a signal cable is to be connected in addition to
the fieldbus cable.
Damage to push-in terminals by jamming of wire end sleeves with the housing!
Replacement of the complete component is required.
→
Use wire end sleeves with smooth surface.
→
Always press the push-in terminals completely down using a screwdriver and
always carefully remove signal cables.
→
It must be possible to pull out the signal cable without resistance when the push-
in terminal held down.
Information: To avoid unevenness at wire end sleeve, AUMA recommends
using the Crimpfox 6 model by Phoenix Contact as suitable crimping pliers.
Figure 3: Connect signal cables
Table 4:
Terminal cross sections
Cross section
Wire type
Designation
max [mm²]
min [mm²]
1.5
0.2
solid
I/O signal cable
1.5
0.2
flexible
1.5
0.2
flexible with wire end
sleeve without plastic
sleeve
AWG 16
AWG 24
AWG
10. Connect fieldbus cables.
Refer to subsequent chapter!