Shield connection
3.
Remove fieldbus cable shield at a short section as shown and connect to shield
connection. Ensure absence of electrical contact to the terminal.
Information: If the cables are too thin to be clamped, fold over the shielding
and clamp it underneath.
Information: Strain relieve must always be made via cable glands. For this,
the shielding connection may not be used.
Figure 5: Shield connection
Fieldbus cables
4.
Connect fieldbus cables: Connect green wires with green terminal and red wires
with red terminal.
Table 5:
Terminal cross sections
Cross section
Wire type
Designation
max. [mm²]
min. [mm²]
1.5
0.5
solid
Fieldbus cables
1.5
0.5
flexible
1.0
0.5
flexible with wire end
sleeve without plastic
sleeve
AWG 16
AWG 20
AWG
Bus termination
5.
If the actuator is the last fieldbus device within the fieldbus segment: Activate
parameter or function
PRM_5559 Bus termination channel 1
via AUMA Assistant
App or AUMA CDT software.
Information: As soon as the bus termination is active, the connection to the
next fieldbus device is automatically interrupted to avoid multiple terminations.
The bus termination is deactivated when leaving the factory.
6.
If the PE conductor has been removed from the cover, it must be tightened
applying 2.2 Nm tightening torque prior to re-placing the cover.
7.
Fasten cable glands with the torque as specified by the manufacturer to ensure
respect of required enclosure protection.
8.
Connect power supply.
If the end position setting is carried out with the internal operation buttons
following the connection to the power supply: Do not close cover!
8
Connect fieldbus cables